10. Technical Data

Power
supply
Remote
signalling
contact
Interface
(COM)
Ambient
conditions
Installation
Enclosure material
Degree of protection
Dimensions
Weight
Standards
Technical Data
Terminal designation
Nominal voltage (range) U
Nominal current I
N
Insulation
Polyswitch fuse
Terminal designation at the
base part
Switching voltage / current
Insulation
Terminal designation
Insulation
Termination
Bus address
Operating temperature range
Standard
Extended
Altitude up to 2000 m,
exceeding 2000 m,
on
Width
Depth without connections
Height above DIN rail
Safety
EMC
DRC MCM XT
Pin +/-, -/+
24 (18...48) V d.c.
N
80 (100...60) mA
None
0,3A, 60V / I
BR
Pin 13,14 (make contact, no)
Pin 21,22 (break contact, nc)
250 V a.c. / 70 mA
350 V d.c. / 120 mA
max. 300 mW
1500 V a.c.
Pin A (+Data), B (-Data)
RS 485, half-duplex (HD)
None
R T = 120 Ω can be deactivated via
jumper/switch (depending on the
device version)
Adjustable via DIP switch
- 20... + 60° C (1...10 SPD)
- 40... + 80° C (1...8 SPD)
if: U
> 33 V
FM
if: U
< 33 V
FM
35 mm metal DIN rail in accordance
with EN 60715
Polyamid PA 6.6 (RAL 7035)
IP 20
12 mm (2/3 mod., DIN 43880)
90 mm
66 mm
62 g
EN 61010-1 (electrical equipment)
EN 61000-6-2 (immunity)
EN 61000-6-3 (emissions)
max: 10 A
or 70 V d.c.
rms
or 70 V d.c.
rms