3. Wiring

Optional remote signalling contakt
Galvanically isolated switch contacts
integrated in the DRC MCM XT monitoring
module.
max. 350 V d.c. / 120 mA
250 V a.c. / 70 mA
Pin: 13-14 make contact (no)
21-22 breake contact (nc)
*) Illustration of the switch contacts in their normal state (all SPD to be monitored
are OK) with applied supply voltage and plugged-in DRC MCM XT.
max. 0.4 Nm
3.5 in-Ibs
Note:
Non-sheathed cables of intrinsically and non-intrinsically safe circuits which are routed in the same conductor bundle or
cable duct have to be isolated by means of an insulating layer or an earthed metal intermediate layer in accordance with
EN 60079-14. Isolation is not required if sheathed cables or cable shields are used in intrinsically or non-intrinsically safe
circuits.
4. Configuration
Select a bus/MCM
address (1...15)
Dezimal
Dual-Code
Wertigkeit
8
4
2
1
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
5
0
1
0
1
6
0
1
1
0
7
0
1
1
1
8
1
0
0
0
9
1
0
0
1
1 0
1
0
1
0
1 1
1
0
1
1
1 2
1
1
0
0
1 3
1
1
0
1
1 4
1
1
1
0
1 5
1
1
1
1
Bus termination (R T )
Activation/deactivation of the bus
termination for the DRC MCM XT
monitoring module
Jumper
Note:
The bus termination can only be activated/deactivated via jumper or slide switch
if the plug-in part is removed!
14
22
13
21
size 0
1*
1*
Dezimal
0 0 0 1
0 0 0 1
1 0 1 0
1 0 1 0
Dual
DIP switch
0 = Off
8 4 2 1 8 4 2 1
1 = On
Tipp:
Use tweezers!
Off
On
Jumper
-/+ d.c.
B
*)
*)
+/- d.c.
A
max. 2.5 mm²
AWG 14
Set the number of
10*
10*
SPDs to be monitored
(max. 10)
*) Example
Slide switch
Voltage Supply
UN 18...48 V DC; max. 100 mA
Pin: +/-; -/+
Recommendation DEHN:
power supply unit
PSU DC24 30W (Part No. 910 499)
Serial RS-485 interface
(only in case of bus connection)
Pin A (+data)
Pin B (-data)
Recommendation: twisted two-wire
cables should be used as a standard
Attach number label for
configured bus/MCM address.
DEHNrecord
DRC MCM XT
BS BA1 BA15 BXT
marking system
Off
Switch
On
page 4