Programming Spds With Bus/Mcm Address And Position Number - dehn DEHNrecord DRC MCM XT Quick Start Manual

Test device
Hide thumbs Also See for DEHNrecord DRC MCM XT:
Table of Contents

Advertisement

Available languages

Available languages

Quick Start Guide DEHNrecord DRC MCM XT

5. Programming SPDs with bus/MCM address and position number

Programming via handheld reader
DRC LC M3 ≥ version 1.1.02 or
DRC LC M3+ ≥ version 1.2.00
5.1 Programming SPDs via DRC LC M3+ handheld reader DRC LC M3+ (operating mode: DRC MCM)
Note:
When programming SPDs via the DRC LC M3 handheld reader, please observe
operating manual BA 1670/V 1.1.01 "Extension for Stationary Monitoring Device DRC MCM XT".
page 5
Programming
Programmierung
DRC LC M3/M3+
see 5.1
activate
SHOW
function
DRC MCM:
Program SPD
ADR=xy
Prog. SPD --> OK
- Programming -
Please wait!
LifeCheck OK
ADR=xy
no
programmiert
PC + Software
via
via
Programmierung über PC mit Software
"Status Display + Service Console" software
MCM
MCM
R T =On
R T =On
siehe 5.2
see 5.2
min. 2 sec.
DRC MCM XT
OK
9
9
0
0
SPD=NN
OK
OK
SPD=NN
yes
all SPDs
alle SPD's
programmed ?
01 - nn
?
min. 2 sec.
Programming via PC using the
Service Console
RS-485
RS-485
R T =On
R T =On
USB
USB
Programming via DRC MCM XT
by pressing the "SHOW" button
device software
see 5.3
Select a menu
and open it
Enter bus/MCM address and SPD No.
Switch between bus address and SPD No.
Snap the sensor onto the SPD to be
programmed and do not remove it
during the programming process.
SPD is not plugged into the base part!
Start programming
Programming in progress
Confirm programming process:
- LifeCheck OK, successful
- Replace SPD, repeat programming
Labels:
to be attached for programmed password
(bus/MCM address • position number)
Programming
Programmende
finished
Deactivate
Master
MCM
MCM
deaktivieren
Master
version 1.008