Installing the distribution header
1 . Select the reducer that fits the diameter of the pipe .
Pipe*
To outdoor unit
Socket
<Liquid side>
❇ Pipe : Separately purchased item
2 . If the number of connected indoor unit is fewer than ports on the distribution header, block the unused ports with
caps .
Welding part
Connect in
order
<Liquid side>
• For A~J type distribution header :
Connect the distribution header to the connection pipe with the provided reducer .
NOTE
• For K~Z type distribution headers :
Cut the provided socket, according to the diameter of the connection pipe, before connecting it .
• Connect the indoor units in order, while respecting the direction of the arrow shown in the illustration .
• When indoor units are connected to same distribution head, indoor unit must be connected in order of
CAUTION
their capacity, from largest to smallest .
DVM S HE_IM_DB68-05461A-08_EN.indd 63
Provided item
Socket
Pipe*
To indoor unit
Provided
item
Case of blocking the unused
distribution header ports
Pipe*
To outdoor unit
Socket
<Gas side>
Connect in
order
Socket
Pipe *
To indoor unit
Case of blocking the unused
distribution header ports
<Gas side>
Over 10~15mm