Samsung AM JXVHGH Series Installation Manual page 42

Table of Contents

Advertisement

Refrigerant pipe installation
H/R
33 .6 kW 40 .0 kW
61 .6 kW
(2)
(1)
(C)
(A)
(B)
Size of the pipe connected to the outdoor unit (A)
Select the size of the pipe according to the below table .
Outdoor unit capacity
(kW)
22 .4 kW
28 .0 kW
33 .6 kW
40 .0 kW
45 .0 kW
50 .4 kW
56 .0 kW
61 .6 kW
67 .2 kW
72 .8 kW ~ 84 .0 kW
89 .6 kW ~ 95 .2 kW
101 .6 kW
106 .6 kW ~ 135 .2 kW
140 .2 kW ~ 168 .2 kW
173 .6 kW ~ 224 .8 kW
Note1) If Ø 25 .40 pipe is not available on site, use Ø 28 .58 pipe .
❇ For HR model, only increase the size of the liquid pipe If pipe length exceeds 90m
42
DVM S HE_IM_DB68-05461A-08_EN.indd 42
Ex.) 135.2 kW
Capacity (kW)
(D)
33 .6 kW
(3)
73 .6 kW
(E)
135 .2 kW
(F)
Main pipe length within 90m
Liquid pipe
Low pressure
(mm)
gas pipe (mm)
Ø 19 .05
Ø 9 .52
Ø 22 .22
Ø 12 .70
Ø 28 .58
Ø 15 .88
Ø 34 .92
Ø 19 .05
Ø 41 .28
Ø 22 .22
Ø 53 .98
No.
Liquid pipe
(1)
Ø 12 .70
(2)
Ø 19 .05
(3)
Ø 19 .05
Size Up (Main pipe length over 90m)
High pressure
Liquid pipe
gas pipe (mm)
(mm)
Ø 15 .88
Ø 12 .70
Ø 19 .05
Ø 15 .88
Ø 22 .22
Ø 19 .05
Ø 28 .58
Ø 22 .22
Ø 34 .92
Ø 41 .28
Ø 25 .40
Pipe size (mm)
High pressure
Gas pipe
gas pipe
Ø 28 .58
Ø 19 .05
Ø 34 .92
Ø 28 .58
Ø 41 .28
Ø 34 .92
Low pressure
High pressure
gas pipe (mm)
gas pipe (mm)
Ø 19 .05
Ø 15 .88
Ø 22 .22
Ø 19 .05
Ø 22 .22
Ø 28 .58
Ø 28 .58
Ø 34 .92
Ø 41 .28
Ø 34 .92
Ø 53 .98
Ø 41 .28