Samsung AM JXVHGH Series Installation Manual page 58

Table of Contents

Advertisement

Refrigerant pipe installation
Allowable length of the refrigerant pipe and the installation examples
H/P
Classification
Installing only with
Y-joint
Installing with Y-joint
and distribution
header
Indoor unit
Installing only with
distribution header
Classification
Outdoor unit ~
Indoor unit
Maximum
allowable
length of
pipe
Outdoor unit
~ Outdoor
unit (Module
installation)
58
DVM S HE_IM_DB68-05461A-08_EN.indd 58
Single Installation
Outdoor unit
Branch joint
Indoor unit
Outdoor unit
Branch joint
Distribution header
Outdoor unit
Distribution header
Indoor unit
Actual
200m and
length
below
(Equivalent
(220m and
length)
below)
Total length
1,000 m or
of pipe (m)
less
Pipe length
10 m or less
Equivalent
13 m or less
length
Module installation
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Example
Installing only
a+b+c+d+e+f+g+p ≤
with Y-joint
200m(220m)
Installing with
a+b+h ≤ 200m (220m),
Y-joint and
distribution
a+i+k ≤ 200m (220m)
header
Installing only
with distribution
a+i ≤ 200m (220m)
header
Installing only
a+b+c+d+e+f+g+h+i+
with Y-joint
j+k+l+m+n+p ≤ 1000m
Installing with
a+b+c+d+e+f+g+h+i+j+k
Y-joint and
distribution
≤ 1000m
header
Installing only
a+b+c+d+e+f+g+h+i
with distribution
≤ 1000m
header
x ≤ 10 m, y ≤ 10m, z ≤ 10 m
x ≤ 13 m, y ≤ 13m, z ≤ 13 m
Branch joint
Distribution header
Branch joint
Distribution header
Remarks
Equivalent length
Y-joint: 0 . 5 m,
Distribution
header: 1 m
-
-
-
2017-03-24 오후 1:38:28

Advertisement

Table of Contents
loading

This manual is also suitable for:

Am jxvhgr seriesAm hxvagh seriesAm100jxvagh/euAm120jxvagh/euAm140jxvagh/euAm160jxvagh/eu ... Show all

Table of Contents