f Branch joint (E)
X
Select a branch joint according to the sum of indoor unit capacity which will be connected after the branch .
❇ However, if the size of the pipe between branch joints (E) is bigger than the size of the pipe connected to the
outdoor unit (D), apply the pipe size (D) .
1) Y-joint
Classification
Y-joint (E)
2) Distribution header
Classification
Distribution header (E)
DVM S HE_IM_DB68-05461A-08_EN.indd 41
Model name
MXJ-YA1509M
MXJ-YA2512M
MXJ-YA2812M
MXJ-YA2815M
MXJ-YA3419M
MXJ-YA4119M
MXJ-YA4422M
Model name
MXJ-HA2512M
MXJ-HA3115M
MXJ-HA3819M
Specification (kW)
15 .0 kW and below
Over 15 .0 kW ~ 40 .0 kW and below
Over 40 .0 kW ~ 45 .0 kW and below
Over 45 .0 kW ~ 70 .3 kW and below
Over 70 .3 kW ~ 98 .4 kW and below
Over 98 .4 kW ~ 135 .2 kW and below
Over 135 .2 kW
Specification (kW)
45 .0 kW and below (for 4 rooms)
70 .3 kW and below (for 8 rooms)
Over 70 .3 kW ~ 135 .2 kW and below
(for 8 rooms)
2017-03-24 오후 1:38:20