Samsung AM JXVHGH Series Installation Manual page 61

Table of Contents

Advertisement

Classification
Outdoor unit ~
Indoor unit
Indoor unit ~
Maximum
Indoor unit
allowable
height
Indoor unit ~
difference
Indoor unit
(in one MCU)
MCU ~ MCU
Maximum
allowable
First branch
length after
joint ~ Farthest
branch
Indoor unit
joint
EEV Kit
EEV kit ~
Actual pipe
Indoor unit
length
❇ Please refer to the EEV Kit manual .
Note 1) When indoor unit is located at higher level than outdoor unit, allowable height difference is 110m, (If the height difference is over
40m, contact your local dealer for more information . ) but when the indoor unit is located at lower level than outdoor unit, allowable
height difference is 110m (If the height difference is over 50m, need to decide whether to install PDM kit or not . )
Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A
Note 2) Required condition
Classification
First branch
45 m ≤ b+h+k, l+m+q, l+r ≤ 90 m : Size of the branch liquid and
joint ~ Farthest
low pressure gas pipes (b, l, m) must be increased by 1 grade .
Indoor unit
If the size of pipe (main pipe), between the first branch joint
and the outdoor unit, is not increased by 1 grade, a+(b+l+m)
x2+c+d+e+f+g+h+i+j+k+n+o+p+q+r ≤ 1000 m
Total length of
extended pipe
If the size of pipe (main pipe), between the first branch joint
and the outdoor unit, is increased by 1 grade, (a+b+l+m)
x2+c+d+e+f+g+h+i+j+k+n+o+p+q+r ≤ 1000 m
MCU ~ Each
c+d, c+e, c+f, g, h+i, h+j, h+k, n, o, p, q, r ≤ 45 m
indoor unit
Difference between the distance of the outdoor unit to the farthest indoor unit and
nearest indoor unit ≤ 45 (a+b+h+k) - (a+b+c+d) ≤ 45
Note 3) For indoor units to which no MCU is connected, be sure to set their options to "Cooling only indoor unit, " and then connect them to a
low pressure gas pipe and a liquid pipe . Be sure to combine the cooling only indoor units so that their total capacity becomes 50% or
less of the total capacity of all indoor units .
Note 4) In case of connecting more than one indoor unit in one MCU Port, the below indoor units cannot be combined . ERV plus
(AM
FNKDE
✴✴✴
✴✴
(MXD-K
AN, MCM-D
✴✴✴
Note 5) In case of connecting two MCU ports with Y-joint, the indoor units cannot be combined to more than one .
DVM S HE_IM_DB68-05461A-08_EN.indd 61
110 m / 110 m
H1 ≤ 110 m / 110 m
Note 1)
40 m or less
H2 ≤ 40 m
But, when AM✴✴✴✴NQDEH✴ / AM✴✴✴JNV✴ is installed, H2 is 15
Pipe length
m or less .
15 m or less
H3 ≤ 15 m
30 m or less
H4 ≤ 30 m
Installing only with MCU
45 m or less
Installing with MCU
Pipe length
and Y-joint
45 ~ 90 m
Note 2)
MEV-E24SA
2 m
MEV-E32SA
MXD-E24K132A
MXD-E24K200A
MXD-E32K200A
20 m or less
MXD-E24K232A
MXD-E24K300A
MXD-E32K222A
MXD-E32K300A
Condition
), OAP duct(AM
JNEPE
), Hydro Unit HE(AM
✴✴✴
✴✴
N)
✴✴✴
Example
g+j ≤ 45 m
b+h+k ≤ 45 m
l+m+q ≤ 45 m
l+r ≤ 45 m
Required conditions must be satisfied
Model name
1 indoor
2 indoor
3 indoor
FNBD
), Hydro Unit HT(AM
✴✴✴
✴✴
Remarks
Remarkers
Apply to products without EEV
(Wall mount & ceiling)
Example
FNBF
), AHU kit
✴✴✴
✴✴
61