Samsung AM JXVHGH Series Installation Manual page 102

Table of Contents

Advertisement

Setting outdoor unit option switch and key function
K2 (Number of
press)
1 time
2 times
3 times
4 times
H/P: Automatic setting of operation mode (Cooling/
5 times
6 times
7 times
8 times
9 times
10 times
11 times
12 times
A type PBA
13 times
B type PBA
14 times
B type PBA
❇ During "Discharge mode of DC link voltage", voltage of INV1 and INV2 will be displayed alternately .
❇ Even when the outdoor unit power is off, it is dangerous when you come in contact with inverter PCB and fan PCB
since they are charged with high DC voltage .
❇ When pressing K2 key 9 to 12 times without inverter checker, error code can be displayed on segment even though
the outdoor unit is normal .
❇ When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/
repairing them . (Wait for more than 15 minutes to allow it to discharge naturally .)
❇ When there were error, 'Discharge mode of DC link voltage' may not have been effective . Especially if error E464
and E364 have been occurred, power element might be damaged by fire and therefore, do not use the 'Discharge
mode of DC link voltage' .
❇ If the 1st-generation MCU is installed, the Auto pipe pairing operation can not be used .
If the 2nd-generation MCU is installed, the Checking the pipe connection can not be used .
- 1st-generation MCU : MCU-S*NEE*N, MCU-S2NEK1N
- 2nd-generation MCU : MCU-S*NEK2N,MCU-S4NEK3N,MCU-S1NEK1N
❇ If there is an A type PBA among the outdoor units installed as a module, the Auto pipe pairing operation can not
be used .
K3 (Number of
press)
1 time
102
DVM S HE_IM_DB68-05461A-08_EN.indd 102
KEY operation
Refrigerant charging in Cooling mode
Trial operation in Cooling mode
Pump down all units in Cooling mode
H/R: Checking the pipe connection
Heating) for trial operation
Checking the amount of refrigerant
Discharge mode of DC link voltage
Forced defrost operation
Forced oil collection
Inverter compressor 1 check
Inverter compressor 2 check
Fan 1 check
Fan 2 check
End key operation
H/R : Auto pipe pairing,
H/P : Unused
End key operation
KEY operation
Initialize (Reset) setting
Display on segment
"K" "5" "BLANK" "BLANK"
"K" "6" "BLANK" "BLANK"
"K" "7" "BLANK" "BLANK"
"K" "8" "BLANK" "BLANK"
"K" "9" X X (Display of last two digits may differ
depending on the progress)
"K" "A" "BLANK" "BLANK"
"K" "B" "BLANK" "BLANK"
"K" "C" "BLANK" "BLANK"
"K" "D" "BLANK" "BLANK"
"K" "E" "BLANK" "BLANK"
"K" "F" "BLANK" "BLANK"
"K" "G" "BLANK" "BLANK"
"K" "H" X X (Display of last two digits may differ
depending on the progress)
Display on segment
Same as initial state
2017-03-24 오후 1:38:46