STEP 14A
STEP 14A. PILOT VALVE - OHM TEST. If pilot assembly is sparking but no pilot flame
is established, disconnect the pilot valve solenoid leads. Using a multimeter, (set to read
ohms) test for 20* ohms resistance +/- 5 through the solenoid coil.
IF
The meter dose not read 20 ohms plus or
minus 5:
The meter does read 20 ohms plus or
minus 5:
Technical Training Department
Ashland City, TN ©2003
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
PILOT VALVE - OHM TEST
SBD 120 – 400 GAS VALVE
THEN
Replace gas valve
Gas valve should work. Also check that
pilot gas is present and pilot tube or
orifice are not blocked