Juniper QFX5120 Series Hardware Manual page 101

Hide thumbs Also See for QFX5120 Series:
Table of Contents

Advertisement

source (A) to one power supply and connect source (B) to the second power supply. This configuration
provides the commonly deployed A/B feed redundancy for the system.
The terminal block of the power supply has four terminals labeled V+, V+, V–, and V– for connecting
DC power source cables labeled positive (+) and negative (–). The V+ terminals are shunted internally
together, as are the V- terminals.
QFX5120-48Y switch.
CAUTION:
include a circuit breaker.
Do not connect two sources to a single power supply because doing so can potentially
cause circulating current in feed wires whenever there is any difference in the voltage
of the two sources.
a. Secure the ring lug of the positive (+) DC power source cable to the V+ terminal on the DC power
supply.
b. Secure the ring lug of the negative (–) DC power source cable to the V– terminal on the DC power
supply.
c. Tighten the screws on the power supply terminals until snug using the screwdriver. Do not
overtighten; apply between 5 in-lb (0.56 Nm) and 6 in-lb (0.68 Nm) of torque to the screws.
Figure 50 on page
The connection between each power source and power supply must
105shows the DC power supply faceplate of a
104

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents