Load Limit; Child-Proofing - Siemens RVD240 Basic Documentation

District heating and domestic hot water controller
Table of Contents

Advertisement

Mode of operation
Calculation of the set-
ting value
74/126
Siemens Building Technologies
HVAC Products
When the plant is started up, the assumption is made that the maximum stroke be 50 %.
If the controller opens the actuator by more than 50 %, the stroke model continually ad-
justs the current maximum stroke "towards 100 %". At midnight, the current stroke is re-
duced by 1 %. If the plant is not in use for a longer period of time, the minimum is 20 %.

18.7.2 Load limit

The flow switch delivers fast information, independent of the d.h.w. flow sensor. This
ensures that the entire heat on the heat exchanger's secondary side is exchanged be-
fore the control of the primary valve is passed to the d.h.w. control.
As soon as d.h.w. is consumed, the flow switch opens primary valve Y5 for a certain
period of time, independent of the flow temperature. This opening time can be set with
the load limit setting on operating line 124. The setting is to be made in % of the maxi-
mum stroke.
Normally, in summer operation, the valve opening required for 100 % load is about 80 %.
This percentage is called the design point and must be included in the calculations.
The load limit can be calculated according to the following formula:
Load limit =
d.h.w. consumption × opening time × design point
Example of calculating the load limit to be set for a heat exchanger with the following
characteristics:
Water content on the secondary side
Average d.h.w. consumption
Opening time of d.h.w. actuator
Design point
Load limit
=
0.14 × 35 × 0.8
This value is used as a guide value and can vary depending on the plant's hydraulic
layout. It is recommended to start with the calculated load limit and then
• decrease the value if the d.h.w. flow temperature significantly overshoots after d.h.w.
consumption
• increase the value if the d.h.w. flow temperature significantly undershoots
After the load limit is reached, the control system will take on control of the actuator on
the primary side.
The end of d.h.w. consumption is also detected by the flow switch and actuator Y5 on
the primary side will be driven to the fully closed position.

18.7.3 Child-proofing

If the d.h.w. tap is repeatedly opened (e.g. by children playing with the tap), the child-
proofing function prevents the load limit function from being executed more often than
necessary, thus preventing excessive d.h.w. temperatures.
If, within a period of 10 seconds, the d.h.w. tap is opened more than twice, the control-
ler will ensure d.h.w. heating without the support of the load limit function.
Basic documentation RVD240
18 Function block Valve actuator d.h.w.
heat exchanger volume
= 1.0 liter
= 0.14 liters / second
= 35 seconds
= 80 % (0.8)
1,0
× 100 = 25 %
secondary
CE1P2384en
27.05.2004