14.5

Minimum limitation of the flow temperature

The minimum limit value is to be set on operating line 96. The setting range for the
minimum limit value lies between 8 °C and the maximum limit value (setting on operat-
ing line 95).
At the limit value, the heating curve runs horizontally. This means that the flow tem-
perature setpoint cannot fall below the minimum value.
This function can be deactivated (entry of --- on operating line 96).
Basic documentation RVD240
14 Function block Valve actuator heating circuit
57/126
CE1P2384en