4.3 Setting the heating on the
Econo model
The setting of the Econo model's water-heat-
ed air heater for reheating is performed with a
thermostat that is placed inside the ventilation
unit. The thermostat setting positions
correspond to the following temperatures:
Together with the W5 ventilation unit, you
can use a separate water heated air heater
which is installed in a duct. The air heater is
commissioned and set using a Smart control
panel. Commissioning and setting are
described in the installation, operation and
maintenance instructions for the air heater.
The duct mounted air heater is optional
equipment: SDHW160.
4.4 Manual bypass damper
The W3/W4 ventilation unit is also available
with a manual summer bypass damper for the
heat exchanger. The bypass of air past the heat
exchanger is a built-in function in the ventila-
tion unit. This function is used to prevent heat
recovery when it is hot during the summer.
Open the bypass damper in the extract cham-
*
=
8 °C
ber to activate the bypass. Pull the locking pin
1
=
11 °C
ring and turn the damper lever to its lower
2
=
14 °C
position to do this. If the damper is open, the
3
=
17 °C
electric air heater for reheating is disabled.
4
=
20 °C
(5
=
23 °C)
When the next heating season begins, you
(6
=
26 °C)
simply close the bypass damper, so that the
locking pin aligns with the appropriate hole.
Winter mode is marked on the ventilation unit
with a snowflake symbol.
Winter
Summer