Commissioning; K-Factor Setting - Swegon PARAGON d Installation, Commissioning Maintenance

Table of Contents

Advertisement

PARAGON d

Commissioning

K-factor setting

2
q
( )
p =
[Pa]
i
k
q = k· p [l/s]
i
q
p = k
i
p
[Pa]
i
q [l/s]
k = k-factor
Example: To achieve the required flow of 25 l/s at 100 Pa, requires k-factor 2.5
A
Find the product's length from left-hand side of the k-factor table.
B
Read the required k-factor on the row in question.
C
Follow the vertical row and read the number of degrees at the bottom.
D
Loosen the screw located in the knob's groove (the knob then moves to the fully open position, 90°)
E
Turn the knob until the marking "D" reaches the required number of degrees.
In the example from the table for a PARAGON d, length 1100, ø125, k-factor 2,5, turn the knob to 50°.
F
Tighten the screw again when the marking is set on the required number of degrees
K-factor table
k-factor PARAGON d
800
0,5
1
A
1100
0,5
1
1,5
1400
0,5 1
1,5
2 2,5
10
20
30
40
degrees
For K-factor setting, always start at 0 degrees and then continue to the desired value.
The right to design changes is reserved. Current data according to product selection program.
14
Swegon reserves the right to alter specifications.
q=k* p
1,5
2
2,5
B
2
2,5
3
3,5
4
3 3,5 4
4,5 5
50
60
70
80
C
81878102





Knob
max
3
4,5
5,5
6
90
06/11/2021
p
= 100 Pa
i

E
D