T1 sensors: Measured value error due to line resistance:
F [K]
0,6 mm Ø
1.0
0.8
0.6
0.4
0.2
0
-0.1
100
2
L
57
A
Formula: F =
10
A
Cable cross-section in mm
F
Measured temperature error in K
L
Cable length in m
Measured value error of NTC sensors due to line resistance:
The sensors are highly non-linear. But thanks to the high sensor resistance the
errors are very small.
Error compared to T1:
NTC 100K
20°C
x 0.01
100°C
x 0.1
Resistance transmitters (potentiometers):
Measured value error due to line resistance
F [Ohm]
0,6 mm Ø
8
6
4
2
0
-1
100
2
L
Formula: F =
57
A
A
Cable cross-section in mm
F
Measurement error in ohms, due to line resistance (2RL for supply and return
conductor)
L
Cable length in m
Desigo TRA Engineering, mounting and installation
Wiring of field devices (without bus)
1 mm
200
1
2
NTC10K
NTC3K
x 0.1
x 0.3
x 1 (~ equal)
- -
²
1 mm
1,5 mm
2,5 mm
200
300
L [m]
1
2
²
²
1,5 mm
²
2,5 mm
300
L [m]
²
²