Technical Data For The Analog Inputs - Siemens Desigo TRA Engineering, Mounting And Installation Manual

Hide thumbs Also See for Desigo TRA:
Table of Contents

Advertisement

Compensation of the line
resistance
Signal type
Resistance AI 1000 Ohm
Resistance AI 2500 Ohm
Resistance AI 10 kOhm
Resistance AI 100 kOhm
Temperature AI PT1K 375
Temperature AI PT1K 385
Temperature AI Ni1000
LG-Ni 1000)
Temperature AI Ni1000 DIN
Temperature AI T1 (PTC)
Temperature AI NTC 3K
Temperature AI NTC 10K
Temperature AI NTC 100K
Voltage measuring
2)
AI 0-10V
Voltage measuring
2)
AI 0-10V norm
Caution!
Siemens
Building Technologies
8.2.3

Technical data for the analog inputs

1 Ohm, calibrated in the module,
(except for NTC3K, NTC10K, and NTC100K)
TX-I/O
Range
Resolution
(Under / over
3)
range)
0...2500 Ohm
100 mOhm
(0...2650 Ohm)
0...2500 Ohm
100 mOhm
(0...2650 Ohm)
-50...150 °C
10 mK
(-52.5 ...185.0 °C)
0.018 °F
-50...400 °C
20 mK
(-52.5...610°C)
0.036 °F
10 mK
-50...150°C
0.018 °F
(-52.5...155.0 °C)
-50...130 °C
10 mK
0.018 °F
(-52.5...155.0 °C)
1)
-40...115 °C
10 mK
0.018 °F
(-52.5...155°C)
(25°C)
1)
-40 ...125 °C
10 mK
0.018 °F
(-52.5...155°C)
(25°C)
2)
0 ... 10 V
1 mV
(-1.5...11.5 V)
1)
Only with reduced hum injection (details see 7.1.2)
2)
Range monitoring of signal type AI 0-10V:
– TX-I/O: short NEGATIVE signal –3.1 V (open circuit), 0.05 mA (shorted)
– DXR: permanently -1.5 V, 0.008 mA.
If a field device has no power supply, the negative voltage can damage any
polarized components (e.g. capacitors) in the field device.
3)
When the process value is outside the range, a fault message is issued.
Desigo TRA Engineering, mounting and installation
Electrical features of inputs & outputs
DXR2
Range
(Under / over range)
3)
0...1000 Ohm
(0...1050 Ohm)
0...2500 Ohm
(0...2625 Ohm)
0...10 kOhm
(0...10.5 kOhm)
0...100 kOhm
(0...105 kOhm)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
-10...70 °C (-15...75 °C)
14...158 °F (5...167 °F)
2)
0 ... 10 V
(-1.0...11.0 V)
0...100%
(-10...110%)
Resolution
1 Ohm
2.5 Ohm
10 Ohm
100 Ohm
25 mK
0.045 °F
25 mK
0.045 °F
25 mK
0.045 °F
25 mK
0.045 °F
100 mK
0.18 °F
25 mK (25 °C)
0.045 °F (77 °F)
25 mK (25 °C)
0.045 °F (77 °F)
25 mK (25 °C)
0.045 °F (77 °F)
2 mV
2 mV
43 / 84
CM111043en_09
2016-02-22

Hide quick links: