Examples of recommended cable types
Belden
Capacitance
Type
9925
39 pF/m
12 pF/ft
8102NH
41 pF/m
12.5 pF/ft
1419A
43 pF/m
13.1 pF/ft
Siemens
Building Technologies
Non-
Shield
1)
halogen
Foil + Braid
NH
Foil + Braid
Foil
1)
Foil + Braid is recommended for harsh environment (mechanical and
electromagnetic interference, e.g. variable speed drives).
2)
2-pair cable to be used with care because of different color scheme.
The two conductors of the second pair must be wired in parallel to the
Reference terminal to prevent a floating conductor.
3)
Recommended color scheme for wiring.
Observe these rules to prevent communications problems.
3-wire
+
White
Black
Reference
Red
Shield
Drain wire (bare)
Desigo TRA Engineering, mounting and installation
MS/TP networks
Tempe-
Pairs
Color
3)
rature
80
1.5
Black Red White
2)
80
2
Blue White / White Blue
Orange White / White Orange
2)
80
2
Blue White / White Blue
Orange White / White Orange
2 pairs
+
White/blue
Blue/White
Reference
2 Orange conductors,
Shield
Drain wire (bare)
parallel
55 / 84
CM111043en_09
2016-02-22