Mitsubishi MELSEC-F FX3U Series User Manual page 24

Programmable controllers
Hide thumbs Also See for MELSEC-F FX3U Series:
Table of Contents

Advertisement

FX
/FX
Series PLC User's Manual - Analog Control Edition
3U
3UC
Common Items
Type
Voltage/current input/output mixture
FX
-5A
*1
2N
*1
FX
-3A
0N
Temperature sensor input
FX
-8AD
*1
2N
FX
-4AD-TC
*1
2N
FX
-4AD-PT
*1
2N
FX
-2LC
*1
2N
*1. To connect this block to the FX
*2. Refer to the instruction manual of the corresponding product.
A-8
No. of
Range
channels
Voltage:
-10V to +10V DC
Input
4ch
Current:
-20mA to +20mA DC
Voltage:
-10V to +10V DC
Output
1ch
Current:
0mA to 20mA DC
Voltage:
0V to 10V DC
Input
2ch
Current:
4mA to 20mA DC
Voltage:
0V to 10V DC
Output
1ch
Current:
4mA to 20mA DC
Type K:
-100°C to +1200°C
Type J:
-100°C to +600°C
8ch
Type T:
-100°C to +350°C
Type K:
-100°C to +1200°C
4ch
Type J:
-100°C to +600°C
Pt100:
4ch
-100°C to +600°C
Example:
Type K:
-100°C to +1300°C
2ch
Pt100:
-200°C to +600°C
Series PLC, either FX
3UC
Resolution
0.32mV
(with sign, 16 bits)
Mixed use of voltage and current
1.25µA
is possible.
(with sign, 15 bits)
The offset/gain can be adjusted.
5mV
The scaling function is
(with sign, 12 bits)
incorporated.
20µA
(10bits)
40mV
(8bits)
64µA
The input format is common to 2
(8bits)
channels.
The offset/gain can be adjusted.
40mV
(Common to 2 input channels)
(8bits)
64µA
(8bits)
Mixed use of voltage, current,
0.1°C
and thermocouple is possible.
Compatible with thermocouple
0.1°C
types K, J, and T.
The unit can be switched
between "centigrade" and
"Fahrenheit."
0.1°C
The sampling function is
incorporated.
Compatible with thermocouple
0.4°C
types K and J.
The unit can be switched
between "centigrade" and
0.3°C
"Fahrenheit."
Compatible with the platinum
resistance thermometer sensor
(Pt100 or JPt100).
0.2°C to 0.3°C
The unit can be switched
between "centigrade" and
"Fahrenheit."
Compatible with thermocouple
types K, J, R, S, E, T, B, N, PL II,
WRe5-26, U, and L.
Compatible with the platinum
resistance thermometer sensor
(Pt100, JPt100).
The unit can be switched
0.1°C or 1°C
between "centigrade" and
(Depends on the
"Fahrenheit."
sensor input range.)
The temperature adjustment
function (that uses PID operation,
etc.) is incorporated.
The peak disconnection
detection function is
incorporated.
(The CT sensor is needed.)
-CNV-IF or FX
2NC
2 Description of Analog Products
2.2 List of Analog Product Models
2.2 List of Analog Product Models
Refer-
Function
ence
-1PS-5V is needed.
3UC
*2
*2
*2
*2
*2
*2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents