Locating The Connecting Box For The Connection Cable In The Sauna Room; Locat Remote Controlling - Helo PICCOLO Pure Installation And User Manual

Electric sauna heater
Table of Contents

Advertisement

Installation and User Manual Piccolo Pure

2.7. Locating the connecting box for the connection cable in the sauna room

A = Specified minimum safety clearance
1. Recommended location for the connecting box
2. Silumin box recommended in this area.
3. This area should be avoided. Always use a silumin box.
In other areas, use a heat-resisting box (T 125 °C) and heat-resisting cables (T 170 °C). The connection box must be
clear of obstacles. When installing the connection box to zones 2 or 3, refer to the instructions and regulations of the
local energy supplier.

2.8. Locat remote controlling

The Heater can be remotely controlled by connecting a closed contactor, which can be pulse triggered, to connectors 3 and 4 of
a RJ10 circuit board. The recommended cable size is AWG 24 or 26. The maximum length of an AWG 24 cable is 200 m when
using a Pure controller.
The maximum length of an AWG 26 cable is 130 m when using a Pure controller.
Note! The sauna standard requires a door switch if the sauna heater is controlled from outside the sauna.
An indicator light can be connected to the remote button terminal, it will be lit up when the remote command is activated. The
indicator light shows an error by blinking rapidly, this error is caused by keeping the sauna door open for more than 5 minutes,
the sauna heater will be shut down automatically.
The remotely operated sauna heater stays on as long as the setting in the control panel (in private us max 6h). The sauna heat-
er can be shut off at any time by the remote-control device.
Circuit board RJ 10 connectors
NOTE: Incorrect connections may break a circuit board.
Additional sensor (NTC)
Pin 1
Pin 2
NTC 10
kOhm
Pin 3
NTC 10
kOhm
Pin 4
Sensor (Sec/NTC)
Pin 1
End stop
Pin 2
NTC 10
kOhm
Pin 3
NTC 10
kOhm
Pin 4
End stop
Table 3 Coupling order of RJ connectors to
circuit board
Figure 7 Location for the connection box
Pin layout of a RJ10 circuit board connector
Remote control switch (Ext switch)
Pin 1
3.3 V
Pin 2
CPU
Pin 3
To switch
Pin 4
To switch
GND
3.3 V
Control panel RJ 10
CPU
connectors
10V
Figure 8 . Order of RJ 10 connectors. Sensor, Door switch, Remote control,
Additional NTC
3.
1.
2.
Door switch
Pin 1
Pin 2
Alarm LED
GND
Pin 3
switch
12 VDC
Pin 4
switch
7
Pin layout of a RJ10
connector
GND
Door
GND
Door
12 VDC

Advertisement

Table of Contents
loading

Table of Contents