Table Of Light Indicators Of The C6.2 Control Panel - Komfovent Domekt Series User Manual

Hide thumbs Also See for Domekt Series:
Table of Contents

Advertisement

4.2. Table of light indicators of the C6.2 control panel

Since the C6.2 control panel does not have a display, it notifies about operation or malfunctions by means of indicator
LEDs. Layout and description of indication LEDs is presented in Chapter 3.2. Different blinking and colour indicates different
messages.
Indication
Indicator near ON/OFF
button lights up in red.
Blue indicator near one of
ventilation mode buttons is
blinking
Blue indicator light next to
AUTO button lights up
Blue indicator near one of
ventilation mode buttons
lights up
Red indicator for messages
and blue indicator for ventila-
tion mode light up.
Red indicator for messages
and blue indicator for ventila-
tion mode are blinking.
Red message indicator is
blinking
All panel indicators are
blinking
Keypad buttons are inactive
UAB KOMFOVENT we reserve the right to make changes without prior notice
C6M_GUIDE2-19-04
Operation
Device not wor-
Device stopped.
king
Device not wor-
The unit will soon start in a ventilation mode the
king
indicator of which is blinking.
Device not wor-
The device is stopped according to a weekly
king
schedule or because of the air quality function.
Device is working
The unit operates in a ventilation mode the
indicator of which is on.
Device is working
Contaminated air filters or other notifications are
present.
Device is working
Temporary special operating mode that can only
be activated by a service specialist.
Device not wor-
Critical fault messages are present that prevent
king
the unit form working.
Not important
Cable between the device and the panel is dam-
aged or connected incorrectly.
Not important
1. Panel lock activated (see Chapter 3.2.4).
2. Faulty panel.
Possible cause
User's actions
Press ON/OFF button to turn on/off the device.
No actions required.
If you want the unit to operate continuously,
not by a schedule or air quality, press AUTO
button.
No actions required.
To read the exact notification, connect a com-
puter or a smartphone to the unit. Follow the
table of messages in Chapter 4.1.
If the unit has been recently repaired, contact
the person who repaired the unit to determine
if service mode can be disabled. Service mode
is turned off by deleting a message.
To read the exact critical fault message, connect
a computer or a smartphone to the unit. Follow
the table of messages in Chapter 4.1.
Check the control panel wiring following the
"Installation Manual" or contact your installer or
authorised service representative.
1. To unlock the control panel, press ON/OFF
button and the reset button at the same
time and hold for 5 seconds.
2. Contact authorised service.
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents