3.1.6. Air quality control mode activation and settings

If air quality sensors are connected to the main board or impurity control/moisture control function is activated (see "Ad-
vanced Settings"), button "Scheduling" appears instead of "Air quality" button. For more information about the air quality
control function see chapter "Air Quality Control Functions".
To enter desired limits and turn on ventilation by air quality:
1. Press "Menu" button at the bottom of the home screen.
2. Press "Air quality" button.
3. Select a parameter you want to change.
4. Use the arrows to select a desired value and press to confirm.
5. Press a return icon at the top of the screen to return to the home screen.
6. Ventilation by air quality is turned on by pressing AUTO button while the unit is operating in any ventilation mode.
7. If the unit was stopped, pressing AUTO button will call up a message, the confirming of which will activate ventilation
by air quality.
16:30
ECO
UAB KOMFOVENT we reserve the right to make changes without prior notice
C6M_GUIDE2-19-04
INTENSIVE
Air temperature
Tiekiamas srautas
210 m3/h
40,0 °C
Šalinamas srautas
210 m3/h
21,0
Oro temperatūra
20,0 °C
Elektrinis šildytuvas
Įjungta
5,0 °C
Reset settings
Menu
Air Impurity
800 ppm
Overview
Air temperature
20,0 °C
Air quality
Electric heater
On
Settings
TURN OFF
16:30
TURN ON?
IŠJUNGTA
AUTO
ECO
INTENSIVE
Supply flow
300 m3/h
210
60 m3/h
Reset settings
Air quality
Reset settings
AIR QUALITY
AUTO
INTENSIVE
Electric heater
Off
On
Reset settings
Air quality
Air Impurity
1800 ppm
800
200 ppm
Reset settings
13