Input The Local Occupied Schedule; Input Service Configurations - Carrier 19DV Series Installation, Operation And Maintenance Instructions

Hermetic centrifugal liquid chillers dual stage
Table of Contents

Advertisement

Fig 45: main menu – setpoint table icon
The Setpoint screen is displayed (see Fig. 46). Set the base demand limit set point, and either the LCW set point
or the ECW set point. To set a value, press the appropriate set point, enter the value, and press OK. For more
information, see the PIC5+ Control User Manual.
Fig 46: Setpoint table screen

5.8.2 Input the local occupied schedule

Access the schedule screen and set up the occupied time schedule according to the customer's requirements. If
no schedule is available, the default is factory set for 24 hours occupied, 7 days per week including holidays. The
Schedule Menu as well as the Holiday Menu can be reached through the Configuration Menu. When the control
mode is LOCAL SCHEDULE, the chiller will be automatically started if the configured local schedule is occupied
and will be automatically shut down by the unoccupied schedule.
The Network Schedule should be configured if a CCN system is being installed. When control mode is
NETWORK, the chiller can be started and stopped by the CHIL_S_S software point as written by other equipment
through the network command and network schedule.
For more information about setting time schedules, please refer to the PIC5+ Control User Manual.

5.8.3 Input service configurations

For specific values or the following configurations, refer to the chiller performance data or job-specific data sheet:
• password
• log in/logout
• input time and date
• service parameters
• equipment configuration
• automated control test
PASSWORD — The PIC 5+ control system provides different levels of access: Basic access, User access,
Advanced User/ Service access and Factory access. User access provides basic access to the chiller controls.
Advanced User access has access to all Service tables, and Factory user has access to factory tables. The PIC
5+ default password configurations are as follows:
• Basic User: No password required
• User: 1111
• Advanced User / Service Access: 2222
• Factory: 4444
79