Carrier 19DV Series Installation, Operation And Maintenance Instructions page 50

Hermetic centrifugal liquid chillers dual stage
Table of Contents

Advertisement

AI7
J15
4-10
AI8
J15
3-9
AI9
J15
2-8
AI10
J15
1-7
AI11
J10
1-7
AO1
J14
1-4
AO2
J14
2-5
AO3
J14
3-6
DI1
J13
1-5
DI2
J13
2-6
DI3
J13
3-7
DI4
J13
4-8
DO1
J12
6-7
DO2
J12
9-10
DO3
J12
1-2
DO4
J12
4-5
Terminal
IOB3 BLOCK
#
AI1
J16
1-5
AI2
J16
2-6
AI3
J16
3-7
AI4
J16
4-8
AI5
J15
6-12
AI6
J15
5-11
AI7
J15
4-10
AI8
J15
3-9
AI9
J15
2-8
AI10
J15
1-7
AI11
J10
1-7
AO1
J14
1-4
AO2
J14
2-5
AO3
J14
3-6
DI1
J13
1-5
DI2
J13
2-6
DI3
J13
3-7
DI4
J13
4-8
DO1
J12
6-7
DO2
J12
9-10
DO3
J12
1-2
DO4
J12
4-5
Terminal
IOB4 BLOCK
#
AI1
J16
1-5
AI2
J16
2-6
AI3
J16
3-7
AI4
J16
4-8
AI5
J15
6-12
AI6
J15
5-11
AI7
J15
4-10
AI8
J15
3-9
AI9
J15
2-8
AI10
J15
1-7
AI11
J10
1-7
AO1
J14
1-4
AO2
J14
2-5
AO3
J14
3-6
Bearing inlet pressure
Auto Demand limit input
Refrigerant leak sensor
Pump inlet Pressure
Guide Vane1 output
EC Valve Output mA
Liquid Level Switch
High Pressure Switch
Ice build contact
Condenser Control Valve
Evaporator Control Valve
Condenser Filling Valve
Economizer Isolation Valve
Point Description
1st stage Bearing Temp
2nd stage Bearing temp
Bearing Ref Supply Temp
Guide Vane 2 Actual Pos
Remote Reset Sensor
Guide Vane 1 Actual Pos
Common CHWS Temp
Auto Water Temp Reset
Common CHWR Temp
Head Pressure Output
Head Pressure Output 2
Guide Vane 2 Output
Spare safety
Evaporator Drain Valve
Condenser Drain Valve
Chilled water pump
Condenser water pump
Point Description
Entering Evap water pressure EVAP_EWP
Leaving Evap water pressure
Entering Cond water
pressure
Leaving Cond water pressure COND_LWP
Evap water flow
measurement
Cond water flow
measurement
Chilled Water Pump
(Variable)
Condenser Water Pump
(Variable)
Tower Fan (Variable)
BRGI_P
BP70
AUTO_DEM
Auto demand limit
REF_LEAK
PUMPI_P
BP80
GV1_OUT
M67 3-4
HGBP_OUT
Y11 15-16
HF_LS
HF_LS
HP_SW
K2
ICE_CON
COND_CV
CCV1
EVAP_CV
ECV1
COND_FCV
-
ECON_IV
-
Designation for
Point name
wiring diagram
CBH1_T
RT39C
CBH2_T
RT40C
BRGI_T
RT41
GV2_POS
M69 5-6
Remote reset
R_RESET
sensor
GV1_POS
M67 5-6
Common CHWS
CHWS_T
Temp
Auto Chiller Water
AUTO_RES
Temp Reset
Chiller CHWR
CHWR_T
Temp
Condenser sea
HDPV_OUT
water valve
HDPV_OU2
-
GV2_OUT
M69 3-4
SAFETY
Spare safety
EVAP_DCV
-
COND_DCV
-
CHWP
-
CDWP
-
Designation for
Point name
wiring diagram
BP13
EVAP_LWP
BP12
COND_EWP
BP15
BP14
EVAP_FL
-
COND_FL
-
Evaporator pump
CHWP_V
control
Condenser pump
CDWP_V
control
TOW_FAN
-
User option, 4-20 mA - customer
terminals
User option, 4-20 mA / not connected in
std
factory option / 4 - 20 mA
contact NO coming from Safety relay
User option, dry contact / not connected
in std
Option
Option
Comments
with spare
with spare
User option, 5K thermistor / connected
on terminals
Used for lead lag option / connected on
terminals
User option, 4-20 mA / connected on
terminals
Used for lead lag option
4 - 20 mA / connected on terminals
4- 20 mA / Not used yet but can be
used
User option, dry contact NO /
connected on terminals
Not used with new design lubrication
Not used with new design lubrication
User option / not connected
User option / not connected
Comments
User option
User option
User option
User option
User option, 4-20 mA / not connected in
std
User option, 4-20 mA / not connected in
std
User option, 4-20 mA / 0-5 V /
connected on terminals
User option, 4-20 mA / 0-5 V /
connected on terminals
User option, 4-20 mA / 0-5 V / not
connected in std
50