Carrier 19DV Series Installation, Operation And Maintenance Instructions page 51

Hermetic centrifugal liquid chillers dual stage
Table of Contents

Advertisement

DI1
J13
1-5
DI2
J13
2-6
DI3
J13
3-7
DI4
J13
4-8
DO1
J12
6-7
DO2
J12
9-10
DO3
J12
1-2
DO4
J12
4-5
* : chiller status in standard, %capacity load in option.
Power Request Feedback
Customer Alert
Freecooling Start Switch
Free Cooling Mode
Power Request Output
Tower Fan High
Tower Fan Low
Table 13 – PIC 5 – 19DV I/Os mapping list
Point description
Power supply 24AC for Digital Output
Chiller Alarm relay
Chiller water pump
Condenser water pump
Tower fan high
Tower fan low
Feeback run
Evaporator flow switch
Condenser flow switch
Remote contact input
Emergency stop
Ice build contact
Spare safety
Auto demand limit input
Common CHWR Temp
Autowater temp reset
Common CHWS Temp
Remote reset sensor
Chiller status *
Head pressure output
Tower fan command signal
Table 14 – PIC 5 – 19DV I/Os terminal identification
POW_FDB
Power Available
CUS_ALE
ICCP 7-8
FC_SS
SW2
FC_MODE
K120
Power Request
POW_REQ
Output
TFR_HIGH
-
TFR_LOW
-
Type
identification -
power supply
Digital output
Digital output
Digital output
Digital output
Digital output
Digital output
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
Analog input
Analog input
Analog input
Analog input
Analog input
Analog output
Analog output
Analog output
Marine option
Marine option, dry contact, NO,
connected on terminals to ICCP
Marine option, dry contact
Factory option
Marine option
User option / not connected in std
User option / not connected in std
Terminal
TB5
1-2
3-4
9
10
11
12
13-14
15-16
17-18
19-20
21-22
23-24
25-26
35-36
37-38
39-40
41-42
43-44
45-46
47-48
53-54