Values apply at an installation altitude of up to 2000 m.
When determining the required minimum air clearance, the voltage value in the table may be increased
by a factor of 1.1, so that the rated input voltage range is taken into account during general use.
6.5

Connecting the auxiliary circuits

6.5.1

Selecting cables

Take the following criteria into account when selecting the connecting cables for the auxiliary
circuits:
● Rated current
● Rated voltage
● System-dependent conditions, such as ambient temperature, routing type, cable cross-
● Requirements according to IEC/EN 60204‑1
6.5.2

Connecting temperature monitoring for the stator winding

The stator winding is monitored for thermal loading by temperature sensors embedded in the
stator winding.
The connecting cables of the temperature sensors are routed to the main or auxiliary terminal
box, depending on the version. The connection and assignment of the terminals is specified
in the circuit diagram.
Hazard due to electric shock
The installation of the temperature sensors for the winding monitoring with respect to the
winding is implemented according to the requirements for basic insulation. The temperature
sensor connections are located in terminal boxes, safe to touch, and have no protective
separation. This is the reason that in the case of a fault, a hazardous voltage can be present
at the measuring sensor cable. When touched, this can result in death, severe bodily injury
and material damage.
● When connecting the temperature sensor to external temperature monitoring devices,
SIMOTICS TN Series N-compact 1LH8
Operating Instructions 06/2017
≤ 800 V
≤ 1000 V
≤ 1250 V
section as defined by required length of cable, etc.
WARNING
when required, apply additional measures to fully comply with the requirements set out in
IEC 60664-1 or IEC 61800-5-1 "Hazard due to electric shock".
Electrical connection
6.5 Connecting the auxiliary circuits
12 mm
14 mm
18 mm
71