Internal Equipotential Bonding; Connecting The Auxiliary Circuits; Table 6-4 Tightening Torque Of Screws With Ground Terminals - Siemens SIMOTICS DC 1HQ7 Operating Instructions & Installation Instructions

Dc motor
Table of Contents

Advertisement

Electrical connection

6.8 Connecting the auxiliary circuits

Table 6-4
Bolt
M6
M8
M10
Equipotential bonding
Terminals are provided on the bearing shield for the connection of an equipotential bonding
conductor.
6.7

Internal equipotential bonding

The equipotential bonding between the protective conductor terminal in the terminal box and
the motor housing is established through the terminal box fixing screws. These screws are
rated and designed as an "equivalent conductive connection" in relation to the protective
conductor cross-section specified for the phase conductor in standard (IEC / EN 60034-1).
Equipotential bonding
In order to guarantee the current carrying capacity of the connection via the retaining bolts in
the event of a short circuit, make sure that the following conditions are fulfilled:
● Use only original gaskets.
● The contact points underneath the bolt heads or spring lock washers must be bare metal
● The standard cover fixing screws are an adequate equipotential bonding connection
6.8
Connecting the auxiliary circuits
Auxiliary circuit
Terminal strips for cable cross-sections of up to 2.5 mm
circuits, e.g. temperature sensor or anti-condensation heating.
58
Tightening torque of screws with ground terminals
and protected against corrosion.
between the terminal box cover and terminal box housing.
WARNING
Electric shock
If the equipotential bonding connection fails, parts of the machine may become live. If you
touch them, you will receive an electric shock. This could result in death, serious injury or
material damage.
When performing any installation work you must always take care to ensure that all
equipotential bonding connections remain effective.
Screw-in depth
> 9 mm
> 12 mm
> 15 mm
Tightening torque
8 Nm
20 Nm
40 Nm
are provided for connecting auxiliary
2
SIMOTICS DC 1HQ7
Operating Instructions 02/2016

Advertisement

Table of Contents
loading

Table of Contents