Running Applications That Use Internal Variables Only - OEM BL2500 User Manual

Embedded plc z-world single board computer
Table of Contents

Advertisement

PLC BL2500 User's Manual
EMBEDDED

3.2 RUNNING APPLICATIONS THAT USE INTERNAL VARIABLES ONLY

The Target PLC and your PC must be connected through Ethernet, RS232 or RS485. Use the following
procedure to run any sample application that uses only internal variables:
1. Open the ISaGRAF Project Management by double-clicking on the ISaGRAF Projects icon on your
Desktop or selecting Start menu → Programs → ISaGRAF 3.5 → Projects. On the Projects
Management window, double-click on the bottlef project.
2. On the BOTTLEF - Programs window select Debug menu → Link setup. On the PC-PLC link
parameters window enter the Target Slave Number (corresponds to the Modbus Slave number of
the Target PLC) and the Communication port (ETHERNET for Modbus TCP or COM for Modbus RTU
over RS232/RS485):
a) If ETHERNET is selected press Setup button and enter the IP address of the target (default is
192.168.1.100). Press OK button. Press OK button to close the PC-PLC link parameters
window
Caution:
Do not change the port number from 1100 otherwise the Ethernet communication
with the ISaGRAF Workbench will not work. This port is used exclusively by the
communication between ISaGRAF Workbench and the
b) If serial COM port is selected (COM1 – COM4) press Setup button and select either 19200,
9600, 4800, 2400, 1200 or 600 baud rate depending on the current configuration of your
PLC target.
EMBEDDED
Note:
The
EMBEDDED
parameters are fixed: no parity, 8 data bits, 1 stop bit and no flow control.
Note also that ISaGRAF supports serial ports COM1 to COM4. If you are using a
USB-to-serial converter cable check that the com port assigned is between COM1
and COM4. If not, change the serial port settings on your Windows Operating
System (see Section 7.2). Many USB-to-serial converters are assigned to COM5
port or higher after its installation.
3. Select Debug menu → Debug to open the Debugger window. If Debugger window displays
"<application name> active" message, stop the current application that is running by pressing the
on the toolbar or select File menu → Stop application. A "No application" message
Stop button
is displayed.
4. Download the bottlef application by selecting File menu → Download. Select "RABBIT: TIC code for
Rabbit-based controllers" on the Download window and press Download button. A progress bar on
the Debugger window will show the progress of the downloading process. Once the downloading is
completed the application runs immediately and the SpotLight window is displayed. In the
SpotLight, double-click on the START button and press TRUE button. The bottle production will
start.
OEM Technology Solutions
PLC Kernel supports baud rates from 19200 to 600. The other
Running Sample Applications
PLC target.
EMBEDDED
Page 17

Advertisement

Table of Contents
loading

Table of Contents