ALLEN-BRADLEY PANELVIEW COMPONENT C400
OPERATIONAL GUIDE
F.
Temperatures
DRYER INLET TEMP measures the temperature coming into the dryer from the
compressor.
COOLER INLET TEMP measures the temperature going into the cooler.
COOLER OUTLET TEMP measures the temperature coming out of the cooler.
The standard will be a 10 degree approach going through the coolers. Example,
if the water is at 85°F, the temperature of the air coming out of the cooler should
be around 95°F. The outlet temperature should not exceed 100°F.
Temperatures will read either °F or °C, depending on option purchased.
A screen selector list is located at the right of the touch screen and is used to
navigate to the other screens. Use the up or down arrow keys to select a screen
name, then press the enter key.
Reference 230 – for use with Sahara Model HC Heat-of-Compression – no heater
Page 7 of 17
Rev 2
10/17/2013