Section 4
Using the HMI
84
1
GUID-83EF7CC3-C895-41C9-82D7-B868FAAB9568 V2 EN
Figure 78:
Load shed control panel for manual load-shedding
1
Effective Value display shows the 'Priority' or 'Load to be shed' values for manual load-
shedding.
2
Active manual load shed setting display.
•
Manual LS is disabled
•
PML630 Priority setting active
•
PML630 kW setting active
•
COM600 Priority setting active
•
COM600 kW setting active
•
PML630 Priority setting active, COM600 quality bad
•
PML630 kW setting active, COM600 quality bad
The last two options are valid when the manual load shed setting is set
to 'SN Man Prio input' and 'SN Man Pow input' respectively.
3
Write value text box is enabled when the Manual load shed mode setting is set to 'SN Man
Prio input' or 'SN Man Pow input' and input data quality is 'Good'.
1MRS757183 F
PML630/Compact Load-Shedding Solution
Operation Manual
2
3
4
5