Section 5
IED operation
5.2.1
5.2.2
90
Settings for device functionality
Function settings can be edited one by one by navigating to the individual setting
values, for example via the LHMI. The values in other setting groups should be known
before editing a certain setting value.
After completing the editing of setting group values, the new values are activated. The
user can either commit the edited values or discard them.
Settings for different operating conditions
Device settings can be designed for various operation conditions by defining different
setting values to different setting groups. The active setting group can be changed by
the device application or manually via the LHMI, WHMI or PCM600.
The device contains only one setting group by default. The number of
setting groups can be selected from 1 to 4. Setting groups are
applicable only to the overcurrent protection functionality supported
by the PSCSWI function.
1MRS757183 F
PML630/Compact Load-Shedding Solution
Operation Manual