Section 4
Using the HMI
54
Settings
Value
Start value
0.8...10 pu
Start value Mult
0.05...5
Time multiplier
limits to be entered
Operating
ANSI Ext. inv.
curve type
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
Operate delay
0.04 - 200.00
time
Governor mode setting is applicable only for Generator and has no
consequence for other power sources, though the setting is visible and
enabled for all types of power sources.
In case of cPMS - LS configuration B, if the Block override parameter
setting is done for the interconnected grid power source circuit
breaker at any one area, the other interconnected area always
considers the far end circuit breaker position as "Close". "Close" to
"Open" change in circuit breaker position is not communicated to the
other interconnected area.
Description
Start value for over current based slow load shed
operation.
Start value multiplier for over current based slow
load shed operation
Time multiplier
Operating curve type selection
Operate delay time for definite time operation
PML630/Compact Load-Shedding Solution
1MRS757183 F
Operation Manual