All Year Comfort - Swegon GOLD PX Series Operation And Maintenance Instructions

Generation d
Hide thumbs Also See for GOLD PX Series:
Table of Contents

Advertisement

8.11 All Year Comfort

The All Year Comfort function controls the supply flow
temperature to comfort modules, chilled beams, perimeter
climate systems, etc. via regulating valves. Two strap-on
temperature sensors fitted either to the water pipe or the
regulating valve are used for measuring the water tem-
perature.
The function requires the electrical equipment cubicle
accessory (TBLZ-1-59-a-b-cc) for controlling the supply
flow water temperature. The function selector switch of
the electrical equipment cubicle must be set to position 7.
All Year Comfort has functions for outdoor compensation,
room compensation, night compensation, dew point com-
pensation and for controlling pump and valve exercising.
For further information, see the Guide to the All Year
Comfort Function.
Settings:
Value
All Year Comfort
Heating water temperature (°C) 10-80°C
Cooling water temperature (°C) 5-30°C
Outdoor comp. Heat. water Active
Outdoor temp. (X1) (°C)
Heating water (Y1)(°C)
Outdoor temp. (X2)(°C)
Heating water (Y2)(°C)
Outdoor temp. (X3)(°C)
Heating water (Y3)(°C)
Outdoor comp., Cool. water Active
Outdoor temp. (X1) (°C)
Cooling water (Y1)(°C)
Outdoor temp. (X2)(°C)
Cooling water (Y2)(°C)
Outdoor temp. (X3)(°C)
Cooling water (Y3)(°C)
Room comp., Heating water Active
Room temperature (°C)
P-band (°C)
Night blocking
Room comp., Cooling water Active
Room temperature (°C)
P-band(°C)
Night blocking
night comp., heating water
Temp. comp. (°C)
night comp., Cooling water
Temp. comp. (°C)
We reserve the right to alter specifications without notice.
Setting
Factory
range
settings
Inactive
Inactive
Cooling
Heating
Cool.+Heat.
30
14
Inactive
Inactive
-40 - 40°C
-20
10 - 80°C
40
-40 - 40°C
5
10 - 80°C
30
-40 - 40°C
15
10 - 80°C
20
Inactive
Inactive
-40 - 40°C
10
5 - 30°C
22
-40 - 40°C
20
5 - 30°C
18
-40 - 40°C
25
5 - 30°C
14
Inactive
Inactive
0 - 40°C
21
1 - 10°C
5
Active
Active
Inactive
Inactive
Inactive
0 - 40°C
21
1 - 10°C
5
Active
Active
Inactive
Active
Inactive
Inactive
-10 - +10°C
-2
Active
Inactive
Inactive
-10-+10 °C
2
INSTALLATION
FUNCTIONS
*FUNCTIONS*
TEMPERATURE
AIR FLOW/PRESSURE
FILTER
OPERATION
HEATING
COOLING
HUMIDITY
ReCO
2
IQnomic Plus
aLL YeaR COMFORt
CONTROL Optimize
night comp.
Channel
Pump op., Heating water
Outdoor temp. Start (°C)
Pump op., Heating water
Outdoor temp. Stop (°C)
Pump op., Cooling water
Outdoor temp. Start (°C)
Pump op., Cooling water
Outdoor temp. Stop (°C)
Pump/valve
Pump alarm, heating water
Valve, heating water
Pump alarm, cooling water
Valve, cooling water
exercising, heating water
Exercising period, (min)
Interval (h)
exercising, Cooling water
Exercising period, (min)
Interval (h)
Dew point comp.
Neutral zone(°C)
Comp. flow (%)
GB.GOLDSK509.091101
*aLL YeaR COMFORt*
FUnCtIOn On/OFF
SettInGS
Inactive
Inactive
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Monday-Friday
Monday-Sunday
Saturday-Sunday
1-2
-40 - 40°C
15
-40 - 40°C
18
-40 - 40°C
-20
-40 - 40°C
-25
Inactive
Inactive
Normally closed
Normally open
Contactor
Active
Inactive
Inactive
Inactive
Inactive
Normally closed
Normally open
Contactor
Active
Inactive
Inactive
Inactive
Inactive
Pump
Pump+Valve
Valve
1-60 min
3
1-168 h
24
Inactive
Inactive
Pump
Pump+Valve
Valve
1-60 min
3
1-168 h
24
Active
Inactive
Inactive
0-5°C
2
0-30%
10
www.swegon.com
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents