Initialize
"Initialize" is a function to return all the settings that the internal control constant are included to
an initial value. Please execute "initialize" only when the error is displayed and this product does
not operate at all.
Please execute the "Reset" function, when you want to return the pressure setting and the switch
setting to an initial value.
No
①
Unlock keys (refer to P9)
②
Press S-key for 2 seconds or more, then go to detail setting mode.
③
To "F99" by using the △ and ▽ keys.
④
Press S-key.
Press △ and ▽ keys for 3 seconds or more.
⑤
(press S-key to ③)
"Initialize" is executed, after 5 seconds.
⑥
(Release keys till less than 5 seconds to ④ )
⑦
Returns to the state immediately after turning on the power supply.
(keys are locked)
LED display
The range of the LED pressure display is different according to the unit of the display.
unit
The range of the
LED pressure display
(Note1) When the display exceeds the upper bound value, "
(Note2) Set the minimum, maximum and switch pressures within the allowable range shown
above.
(Note3) The unit cannot be changed.
Refer to the SMC website
(URL http://www.smcworld.com) for more information
about troubleshooting.
This operation manual refers to all standard types
and is partially applicable to special models.
4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021 JAPAN
Key operation
MPa
0.00 to 3.60
⇔
displayed alternately
is displayed
Turning off for 1 second
2
kgf/cm
0.0 to 36.0
A
:
C hange of "Safety Instructions"
B
P 15 Addition note
:
C
C hange of " Min. press. (F_1) adjusting range"
:
0120-837-838
- 16 -
LED Display
(displayed alternately)
bar
0.0 to 36.0
0 to 522
" is displayed.