Unlock keys (refer to P9)
Press S-key
Set the minimum pressure by using the △
and ▽ keys.
Press S-key
Set the maximum pressure by using the
△ and ▽ keys.
Go to No. ⑪ for monitor output : analogue output (voltage and current) type.
Press S-key
Set the P_1 by using the △ and ▽ keys.
Press S-key
Set the P_2 by using the △ and ▽ keys.
Press S-key
Lock keys (refer to P9)
Minimum pressure (F_1) adjusting range
100%
90%
0%
4
0
0
2. 5
0
(Note1) F_1 is adjustable in a range from 0% to 90% of the rated value.
(Note2) F_2 is adjustable in a range from 10 to 120% of the rated value.
(Note3) Do not input the signal as like output the pressure of more than 100%.
Please use in a range of rating.
(Note4) The difference between F_1 and F_2 is adjustable in a range of 10% of the rated value.
(Note5) The adjustment like making the relation of F_1 > F_2 is not available.
(Note6) The numbers (3.00 etc) on the LED display indicate the secondary pressure.
Mode of switch output
12
20m A
10
20m A
5V
5
10V
* Adjusting range: Refer to Note 1 to 6
* Adjusting range: Refer to Note 1 to 6
Return to (current) pressure display.
Maximum pressure (F_2) adjusting range
120%
100%
10%
0%
4
0
0
0
(Default value : 0%=0.00MPa)
(Default value : 100%=3.00MPa)
- 11 -
(displayed alternately)
(displayed alternately)
(displayed alternately)
(displayed alternately)
12
20m A
10
20m A
2. 5
5V
5
10V