Gas Cooler & Flash Gas Bypass
Pressure Regulating Valves
Type GC and FGB
INSTALLATION AND SERVICING INSTRUCTIONS
SD-398
The Sporlan GC and FGB valve families are stepper motor driven pressure regulating valves engi-
neered specifically for transcritical CO
for application as a Gas Cooler valve, but can also be applied as a Flash Gas Bypass valve. The FGB
family is designed to extend the capacity range of the GC valves when applied as Flash Gas Bypass
valves. Both families are rated for 140 barg (2030 psig) maximum working pressure. Offered with a
PSD4BX3XXXVP Valve Positioner and PSS4B Backup Power Module, the GC/FGB valves are easy to
implement, and feature:
• High resolution actuators with 2500 steps and 7.25 second full stroke actuation
• Uniquely characterized pin and port combinations for excellent full range flow control
• Cartridge valve designs with interchangeable bodies
• Tight seating capability
• Replaceable / serviceable screens (GC only)
For more information on these Sporlan Transcritical CO
INSTALLATION
Valves are shipped fully assembled, but must be disassembled prior to installation.
1.
Supporting the valve body on the provided flats, loosen and remove the motor adapter assem-
bly using the 1-1/2" (38.1mm) hex flats.
GC
NOTE: The motor adapter assemblies are extremely tight, so proper tools are required to support
and loosen the components. Be careful not to warp the body by clamping too tightly.
NOTE (FGB ONLY): If the valve has been energized at any time, the piston must be retracted prior
to disassembly. Failure to do so can permanently damage the valve. The valve pistons are shipped
at approximately half stroke, so if the valve has not been energized, retracting the piston is not
necessary.
(R-744) refrigeration systems. The GC family is designed
2
valves, please refer to Bulletin 100-80.
2

Advertisement

loading

Summary of Contents for Parker GC Series

  • Page 1 Gas Cooler & Flash Gas Bypass Pressure Regulating Valves Type GC and FGB INSTALLATION AND SERVICING INSTRUCTIONS SD-398 The Sporlan GC and FGB valve families are stepper motor driven pressure regulating valves engi- neered specifically for transcritical CO (R-744) refrigeration systems. The GC family is designed for application as a Gas Cooler valve, but can also be applied as a Flash Gas Bypass valve.
  • Page 2 FGB ONLY – Remove the port using a standard 1-1/8” deep well socket. The gasket will now be loose, and should be removed from the body as well. Butt or socket weld the GC valve body into the system piping (1/2”, 3/4” or 1”connection). The FGB body can be installed with a butt weld (1”), or brazed with the ODF (1-1/8”) or ODM (1-3/8”) connection.
  • Page 3 Insert the motor adapter assembly into the valve body, and tighten using the 1-1/2” (38.1mm) hex flats. 55-80 N-m (40-60 ft.-lbs.) 40-60 N-m 55-80 N-m (30-45 ft.-lbs.) (40-60 ft.-lbs.) NOTE (FGB ONLY): If the valve has been energized at any time, the piston must be retracted prior to assembly.
  • Page 4 Parker or its subsidiaries or authorized distributors. To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based upon data or specifications provided by the user, the user is responsible for determining that such data and specifications are suitable and sufficient for all applications and reasonably foreseeable uses of the components or systems.