Boiler Room Requirements - SAS BIO SOLID 19 Operation And Maintenance Manual

Table of Contents

Advertisement

The boiler room in which the central heating boiler is installed must meet
current specific regulations in force in a country of destination (e.g. PN-87/B-02411
Heating. Built in boiler house for solid fuel. Requirements).
NOTICE: Use of mechanical ventilation is unacceptable.
• boilers should be located possibly centrally to heated rooms, and the
boiler should be placed as closely as possible to a chimney;
• an entrance door should open to the outside of the room and must be
constructed of non-flammable materials;
• the boiler room of heat capacity up to 25 kW should be equipped with
supply ventilation in form of a nonclosing aperture of at least 200 cm
• the boiler room of heat capacity above 25 kW should be equipped with
a supply duct of cross-section no less than 50% of a chimney cross-sec-
tion area, however, no less than 20x20 cm with an outlet at a height up to
1 m above the floor level in the back part of the room; a device controlling
air flow should be installed in a supply aperture or duct, however, it sho-
uld not reduce the cross-section to less than 1/5 (no supply ventilation or
its obstruction may result in such events as smoke formation or inability
to reach higher temperature);
• the boiler room of heat capacity up to 25 kW should be equipped with
exhaust ventilation (a duct of non-flammable material) under a room
ceiling of a cross-section no less than 14x14 cm
• the boiler room of heat capacity above 25 kW should be equipped with
an exhaust duct of cross-section no less than 50% of a chimney cross-
-section area, however, no less than 14x14 cm (the exhaust ventilation
removes harmful gases from the room);
• the exhaust ventilation duct should be routed above a roof level and
located close to the chimney. No closing devices should be installed on
the exhaust duct. The ventilation duct must be made of non-flammable
material.
• The boiler room should be provided with natural and artificial lighting.
FOR SAFETY REASONS IT IS RECOMMENDED TO EQUIP THE BO-
ILER ROOM WITH A CARBON OXIDE (CO) AND A SMOKE SEN-
SORS.

7.1. BOILER ROOM REQUIREMENTS