Munters Vortex VX26F1CR User Manual And Installation Manual

Munters Vortex VX26F1CR User Manual And Installation Manual

26"

Advertisement

Quick Links

26" Vortex
Fans
®
VX26F1CR • VX26F1CP
U.S. Patent No. 6386828, 6616404 and 6953320.
R
R
Ventilation Systems
Munters Corporation
FORM: QM1070
Rev.3, February 2010
4215 Legion Dr. Mason, MI 48854-1036 USA
Page 1 of 15
(517) 676-7070
Fax (517) 676-7078
www.munters.us/aerotech

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Vortex VX26F1CR and is the answer not in the manual?

Questions and answers

Summary of Contents for Munters Vortex VX26F1CR

  • Page 1 26" Vortex Fans ® VX26F1CR • VX26F1CP U.S. Patent No. 6386828, 6616404 and 6953320. Ventilation Systems Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA Page 1 of 15 (517) 676-7070 Fax (517) 676-7078 www.munters.us/aerotech...
  • Page 2: Table Of Contents

    Please read all instructions carefully before beginning installation. WARRANTY For Warranty claims information see the "Warranty Claims and Return Policy" form QM1021 available from the Aerotech Ventilation System, Munters Corporation office at 1-800-227-2376 or by e-mail at aerotech@munters.com. Conditions and Limitations: •...
  • Page 3: Unpacking The Equipment

    FAN DIA. (I.D., framed) " 33" 33" " " " " 32 " 26" " " sq. Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA Page 3 of 15 (517) 676-7070 Fax (517) 676-7078 www.munters.us/aerotech...
  • Page 4: Installation Instructions

    Figure 2B 1 x 6 Framing 2 x 4 Framing OUTSIDE INSIDE Figure 3 Figure 2A Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA Page 4 of 15 (517) 676-7070 Fax (517) 676-7078 www.munters.us/aerotech...
  • Page 5 Remove packaging from cone and guard sections. Step 4 Place cone sections on ground with rounded side down. See Figure 4. Figure 1 Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA Page 5 of 15...
  • Page 6 ¼" x ¾" Wafer Head Bolt [B] " Flange Nut [C] Cone Section Figure 5B SIDE VIEw OF 2 CONE SECTIONS Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA Page 6 of 15 (517) 676-7070 Fax (517) 676-7078 www.munters.us/aerotech...
  • Page 7 If fan was ordered with 'PR' style shutter proceed to Step 10. If the 'PV' style shutter was ordered then proceed to Step 12. Figure 7B Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA...
  • Page 8: Pr" Style Shutters

    Installation is now complete, proceed to Electrical Wiring Section. Airfoil Draw Latch Shutter Figure 9 Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA Page 8 of 15 (517) 676-7070 Fax (517) 676-7078...
  • Page 9: Pv" Style Shutters

    See Figure 10B. Installation is now complete, proceed to electrical wiring section. PV Shutter Figure 10A Figure 10B Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA Page 9 of 15 (517) 676-7070 Fax (517) 676-7078 www.munters.us/aerotech...
  • Page 10: Electrical Wiring

    L1 = Line 1 refers to 120 VAC control. N = Neutral L2 = Line 2 G = Ground L3 = Line 3 Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA Page 10 of 15 (517) 676-7070 Fax (517) 676-7078 www.munters.us/aerotech...
  • Page 11: Maintenance

    NEVER CLEAN ELECTRICAL EQUIPMENT WITH A PRESSURE WASHER! Do not power wash. Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA Page 11 of 15...
  • Page 12: Trouble Shooting

    1. Override thermostat set Set to the correct temperature incorrectly 2. Control set for continuous Set speed control correctly operation Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA Page 12 of 15 (517) 676-7070 Fax (517) 676-7078 www.munters.us/aerotech...
  • Page 13: Winterizing Fan

    Aerotech does not endorse any specific snow guard product and no performance warranty is implied. IMPORTANT Aerotech Ventilation Systems Product and System Warranties do not cover cone or fan damage from external sources. Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA...
  • Page 15 Shutter, airfoil w/tie-bars, plastic PV26 Shutter, all plastic FH2119 Right Shutter Clip, AL FH2117 Left shutter clip, AL Munters Corporation FORM: QM1070 Rev.3, February 2010 4215 Legion Dr. Mason, MI 48854-1036 USA Page 15 of 15 (517) 676-7070 Fax (517) 676-7078...