ALARM 164, ATEX ETR cur.lim.alarm
Operating above the characteristic curve for more than 60
s within a period of 600 s activates the alarm and the
frequency converter trips.
WARNING 165, ATEX ETR freq.lim.warning
The frequency converter is running more than 50 s below
the permitted minimum frequency (1-98 ATEX ETR interpol.
points freq. [0]).
ALARM 166, ATEX ETR freq.lim.alarm
The frequency converter has operated more than 60 s (in a
period of 600 s) below the permitted minimum frequency
(1-98 ATEX ETR interpol. points freq. [0]).
ALARM 246, Power card supply
This alarm is only for F Frame frequency converters. It is
equivalent to Alarm 46. The report value in the alarm log
indicates which power module generated the alarm:
7
7
1 = left most inverter module.
2 = middle inverter module in F2 or F4 frequency
converter.
2 = right inverter module in F1 or F3 frequency
converter.
3 = right inverter module in F2 or F4 frequency
converter.
5 = rectifier module.
WARNING 250, New spare part
A component in the frequency converter has been
replaced. Reset the frequency converter for normal
operation.
WARNING 251, New typecode
The power card or other components have been replaced
and the typecode changed. Reset to remove the warning
and resume normal operation.
44
®
VLT
AutomationDrive FC 301/302 Operating Instructions
MG33AN02 - Rev. 2013-09-06