Diagnostics and Troubleshoo...
No.
Text
2049
Power data restarted
2064-2072
H081x: Option in slot x has restarted
2080-2088
H082x: Option in slot x has issued a powerup-wait
2096-2104
H983x: Option in slot x has issued a legal
powerup-wait
2304
Could not read any data from power EEPROM
2305
Missing SW version from power unit
2314
Missing power unit data from power unit
2315
Missing SW version from power unit
2316
Missing lo_statepage from power unit
2324
Power card configuration is determined to be
incorrect at power up
2325
A power card has stopped communicating while
main power is applied
2326
Power card configuration is determined to be
incorrect after the delay for power cards to
register.
2327
Too many power card locations have been
registered as present.
2330
Power size information between the power cards
does not match.
2561
No communication from DSP to ATACD
2562
No communication from ATACD to DSP (state
running)
2816
Stack overflow control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
LCP stack overflow
2821
Serial port overflow
2822
USB port overflow
2836
cfListMempool too small
3072-5122
Parameter value is outside its limits
5123
Option in slot A: Hardware incompatible with
control board hardware
5124
Option in slot B: Hardware incompatible with
control board hardware.
5125
Option in slot C0: Hardware incompatible with
control board hardware.
5126
Option in slot C1: Hardware incompatible with
control board hardware.
5376-6231
Out of memory
Table 7.6 Internal Fault, Code Numbers
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.
®
VLT
AutomationDrive FC 301/302 Operating Instructions
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove short-
circuit connection. Check 5-00 Digital I/O Mode and
5-01 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove short-
circuit connection. Check 5-00 Digital I/O Mode and
5-02 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For X30/6, check the load connected to X30/6 or remove
the short-circuit connection. Check 5-32 Term X30/6 Digi
Out (MCB 101).
For X30/7, check the load connected to X30/7 or remove
the short-circuit connection. Check 5-33 Term X30/7 Digi
Out (MCB 101).
ALARM 43, Ext. supply
MCB 113 Ext. Relay Option is mounted without ext. 24V
DC. Either connect an ext. 24V DC supply or specify that
no external supply is used via 14-80 Option Supplied by
External 24VDC [0]. A change in 14-80 Option Supplied by
External 24VDC requires a power cycle.
ALARM 45, Earth fault 2
Earth (ground) fault.
Troubleshooting
ALARM 46, Power card supply
The supply on the power card is out of range.
There are three power supplies generated by the switch
mode power supply (SMPS) on the power card: 24 V, 5 V,
±18 V. When powered with 24 V DC with the MCB 107
option, only the 24 V and 5 V supplies are monitored.
When powered with three phase mains voltage, all three
supplies are monitored.
Troubleshooting
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. The external
24 V DC back-up power supply may be overloaded,
otherwise contact the Danfoss supplier.
MG33AN02 - Rev. 2013-09-06
Check for proper earthing (grounding) and loose
connections.
Check for proper wire size.
Check motor cables for short-circuits or leakage
currents.
Check for a defective power card.
Check for a defective control card.
Check for a defective option card.
If a 24 V DC power supply is used, verify proper
supply power.
7
7
41