PowerWalker VFI 10K-80K CPG 3 User Manual page 25

Uninterruptible power supply system
Table of Contents

Advertisement

ELECTRICAL
Output Voltage: Select the output rated voltage.
208V , 220V ,230V and 240V.
Output Frequency: Select output rated frequency.
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
CVCF Mode (constant voltage and constant frequency function)
Enable: CVCF function is enabled. The output frequency will be fixed at 50Hz or 60Hz according to
setting of "OP Freq.". The input frequency could be from 46Hz to 64Hz.
Disable: CVCF function is disabled. The output frequency will synchronize with the bypass frequency
within 46~54 Hz for 50Hz system or within 56~64 Hz for 60Hz system. Disable is the default setting.
Bypass Forbid:
Enable: Bypass forbid is enabled. When selected, it's not allowed for running in Bypass mode under any
situations.
Disable: Bypass forbid is disabled. When selected, UPS will run in Bypass mode depending on "Bypass at
UPS off" setting. It is the default setting.
Bypass at UPS off: Select the bypass status when manually turning off the UPS. This setting is only available
when "Bypass forbid." is set to "Disable".
Enable: Bypass enabled. When selected, bypass mode is activated.
Disable: Bypass disabled. When selected, no output through bypass when manually turning off the UPS.
Bypass Voltage Range: Set the bypass voltage range.
L: Low voltage point for bypass. The setting range is 176V ~ 209V
H: High voltage point for bypass. The setting range is 231V ~ 264V
Bypass FRE Range: Set the bypass frequency range.
The acceptable bypass frequency range from 46Hz to 54Hz when UPS is 50Hz system and from 56Hz to 64Hz
Electrical Setting Page 1
Electrical Setting Page 2
22