Demand Limiting; Power Failure Restart Delay; Alarms - Carrier WSHP Open v3 Integration Manual

Hide thumbs Also See for WSHP Open v3:
Table of Contents

Advertisement

Installation

Demand limiting

The WSHP Open can accept 3 levels of demand limit from the BACnet network. In response to a demand limit, the
unit decreases its heating setpoint and increases its cooling setpoint to widen the range, in order to immediately
lower the electrical demand. You can configure the temperature adjustment for both heating and cooling and for
each demand level. You can also set the response to a particular demand level to 0.

Power failure restart delay

The control provides a delay when recovering from a power failure, a shutdown mode, or when transitioning from
unoccupied to occupied mode, in order to prevent excessive demand when many units start simultaneously. Each
unit can be configured for a unique delay between 0 and 600 seconds. The factory-programmed default delay is
60 seconds.

Alarms

Fire/Smoke Detector Alarm – The control monitors the voltage input to J1-9 to detect if a smoke detector or fire
detector NC contact has opened, indicating an alarm condition. The control verifies the presence of 24 Vac on this
input. If the input opens at any time, an alarm is generated after 3 seconds and the equipment (fan, compressor,
aux heat, and damper) immediately shuts down.
Space Temperature Alarms – The control provides the ability to generate an alarm whenever the space
temperature exceeds the alarm setpoint. A separate occupied hysteresis and fixed unoccupied high and low alarm
setpoints are provided. The control provides a 5-minute alarm delay during unoccupied periods. During occupied
periods, the control uses the occupied temperature setpoint and applies the hysteresis value to determine the
alarm setpoints. Whenever occupancy transitions from unoccupied to occupied or the occupied temperature
setpoints are changed, causing an alarm condition to occur, the control automatically calculates an alarm delay
(equivalent to the configured delay time in minutes/ ° F, multiplied by the temperature error, + 15 minutes). This
prevents nuisance alarms whenever an occupancy change occurs and allows time for the unit to correct an
alarming temperature condition.
Condenser Water Temperature Alarm – The control has 4 configurable alarm limits for condenser water
temperature. The control verifies that the water temperature is within operating range (between high and low
limits) for the specific operating mode (heating or cooling) before energizing the compressor. Once the compressor
is started, the condenser water temperature is further monitored to verify that it is within limits to insure sufficient
water is flowing through the coil. If the leaving water temperature rises above or falls below the appropriate limits,
and lasts for more than 15 seconds, an alarm is generated and the compressor shuts down.
Supply Air Temperature Alarm – The control has 2 configurable alarm limits for supply air temperature. The
control verifies that the supply air temperature is within operating range (between high and low limits) whenever
the compressor or auxiliary heat is operating. If the air temperature rises above or falls below the appropriate
limits, and this lasts for more than 5 minutes, an alarm is generated.
High Condensate/Overflow Alarm – The control monitors a discrete input to determine the state of a condensate
level switch. You can configure the input to alarm on either an open or closed switch condition. If this input is in an
alarm state, the control starts a timer, and after the timer exceeds a configurable Condensate Overflow Alarm
Delay limit (10-second default), the control generates an alarm and the unit disables the compressor and fan
outputs.
Fan Status Alarm (optional) – The control generates a fan status alarm if the fan status input detects the fan is
OFF after any fan speed output has been enabled. A 30-second alarm delay is used to allow the fan to start
operation before an alarm condition is detected. The control monitors the fan output and if the fan is operating at
any speed, the fan status must detect the fan is operating.
Compressor Status Alarm – The control generates a compressor failure alarm if the compressor status input
detects the compressor is OFF after the compressor output has been energized. A 6-minute alarm delay is used to
allow the compressor to start (prevents alarms due to timeguard operation) before an alarm condition is detected.
The control monitors the compressor output and if the compressor output is energized, the compressor status
input must detect the compressor operation.
20
WSHP Open v3

Advertisement

Table of Contents
loading

Table of Contents