Figure 45. Typical performance of the heat exchanger, 30 kW heat load
Figure 46. Pressure drop (standard units)
Water specifications for the secondary cooling loop
Important: The water that is being supplied to the heat exchanger must meet the requirements that are
described in this section. Otherwise, system failures might occur over time as a result of any of the
following problems:
v Leaks due to corrosion and pitting of the metal components of the heat exchanger or of the
water-supply system.
v Buildup of scale deposits inside the heat exchanger, which can cause the following problems:
– A reduction in the ability of the heat exchanger to cool the air that is exhausted from the rack