IBM 8408-44E Site And Hardware Planning page 130

Hide thumbs Also See for 8408-44E:
Table of Contents

Advertisement

7109 or 5889 PDU+
Table 131. 7109 or 5889 PDU+ features
PDU Number
Racks usage
7109 or 5889 PDU+
7953-94X, 7965-94Y, 0551, 0553,
and 0555 IBM racks
Table 132. 7109 PDU+ specifications
Characteristics
PDU number
Height
Width
Depth
Additional clearance
Weight (not including power cord)
Weight of power cord (approximate)
Operating temperature at 0 - 914 m (0 - 3000
ft) (room ambient)
Operating temperature at 914 - 2133 m (3000 -
7000 ft) (room ambient)
Operating humidity
Localized air temperature in PDU
Rated frequency (all feature codes)
Circuit breakers
Power outlet
7196 PDU+
Table 133. 7196 PDU+ features
PDU Number
Racks usage
7196 PDU+
7014-B42
Table 134. 7196 PDU+ specifications
Characteristics
PDU number
Height
Width
Depth
Additional clearance
Weight (not including power cord)
Weight of power cord (approximate)
114
Site and hardware planning
Supported power cords (PDU to wall)
"Supported PDU power cords" on page 105
Properties
7109
43.9 mm (1.73 in.)
447 mm (17.6 in.)
350 mm (13.78 in.)
25 mm (0.98 in.) for circuit breakers
3 mm (0.12 in.) for outlets
6.3 kg (13.8 lb)
5.4 kg (11.8 lb)
10°C - 32°C (50°F - 90°F)
10°C - 35°C (50°F - 95°F)
8% - 80% (noncondensing)
60°C (140°F) maximum
50 - 60 Hz
Six double-pole branch rated circuit breakers that are rated at 20 A
12 IEC 320-C13 outlets that are rated at 10 A (VDE) or 15 A
(UL/CSA)
Supported power cords (PDU to wall)
Fixed power cord with IEC 60309, 3P+E, 60 A plug
Properties
7196
43.9 mm (1.73 in.)
447 mm (17.6 in.)
350 mm (13.78 in.)
25 mm (0.98 in.) for circuit breakers
3 mm (0.12 in.) for outlets
6.3 kg (13.8 lb)
5.4 kg (11.8 lb)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

8408-e8ePower systems series

Table of Contents