IBM 8408-44E Site And Hardware Planning page 134

Hide thumbs Also See for 8408-44E:
Table of Contents

Advertisement

The IBM 7188 or 9188 rack-mounted power distribution unit (PDU) contains 12 IEC 320-C13 outlets that
are connected to six 20 amps (A) circuit breakers (two outlets per circuit breaker). The PDU employs an
inlet current that allows various power cord options that are listed in the following chart. Based on the
power cord that is used, the PDU can supply from 24 amps to 63 amps.
Table 139. Power cord options
Feature
code
Power cord description
6489
Power cord, PDU to wall, 4.3 m (14 ft), 230 V ac, 3 phase wye, Souriau UTG, IEC
60309, 3P+N+E plug
6491
Power cord, PDU to wall, 4.3 m (14 ft), 200 - 240 V ac, single phase, Souriau UTG, IEC
60309, P+N+E plug
6492
Power cord, PDU to wall, 4.3 m (14 ft), 200 - 240 V ac, single phase, Souriau UTG, IEC
60309, 2P+E plug
6653
Power cord, PDU to wall, 4.3 m (14 ft), 230 V ac, 3 phase wye, Souriau UTG, IEC
60309, 3P+N+E plug
6654
Power cord, PDU to wall, 4.3 m (14 ft), 200 - 240 V ac, single phase, Souriau UTG,
plug type 12 plug
6655
Power cord, PDU to wall, 4.3 m (14 ft), 200 - 240 V ac, single phase, Souriau UTG,
plug type 40 plug
6656
Power cord, PDU to wall, 4.3 m (14 ft), 200 - 240 V ac, single phase, Souriau UTG, IEC
60309, P+N+E plug
6657
Power cord, PDU to wall, 4.3 m (14 ft), 200 - 240 V ac, single phase, Souriau UTG,
plug type PDL plug
6658
Power cord, PDU to wall, 4.3 m (14 ft), 200 - 240 V ac, single phase, Souriau UTG,
plug type KP plug
6667
Power cord, PDU to wall, 4.3 m (14 ft), 230 - 240 V ac, 3 phase wye, PDL 56P532
Loading requirements
The power loading of the 7188 or 9188 PDU must follow these rules:
1. Total power load that is connected to the PDU must be limited to below the amperage that is listed in
the table.
2. Total power load that is connected to any one circuit breaker must be limited to 16 A (derating of
circuit breaker).
3. Total power load that is connected to any one IEC320-C13 outlet must be limited to 10 A.
Note: The load on the PDU when a dual line configuration is used is only half the total load of the
system. When you are calculating the power load on the PDU, you must include the total power load of
each drawer even if the load is distributed over two PDUs.
Loading sequence
Follow these loading sequence steps:
1. Collect power requirements for all units that are connected to the 7188 or 9188 PDU. See your server
specifications for specific power requirements.
2. Sort list by total power that is required from highest power draw to lowest power draw.
3. Connect highest power drawer to outlet 1 on circuit breaker 1.
4. Connect next highest power drawer to outlet 3 on circuit breaker 2.
5. Connect next highest power drawer to outlet 5 on circuit breaker 3.
118
Site and hardware planning
Amps
96 A (32 A x
3)
63 A
60 A (48 A
derated)
48 A (16 A x
3)
30 A (24 A
derated)
30 A (24 A
derated)
32 A
32 A
30 A (24 A
derated)
96 A (32 A x
3)