Specification Tables - Honeywell CORE Drive Quick Start Manual

Hvac control variable frequency drive
Table of Contents

Advertisement

HONEYWELL CORE DRIVE

SPECIFICATION TABLES

Control Method
Starting Torque
V/F Curve
Speed Response
Ability
Torque Limit
Torque Accuracy
Max. Output
Frequency (Hz)
Frequency Output
Accuracy
Output Frequency
Resolution
Overload Tolerance Normal duty: 120% of rated current for 1 minute
Frequency Setting
Signal
Accel./Deccel. Time 0.00~600.00/0.0~6000.0 seconds
Main control
function
Fan Control
Motor Protection
Over-current
Protection
Over-voltage
Protection
Over-temperature
Protection
Stall Prevention
Restart After
Instantaneous
Power Failure
Grounding Leakage
Current Protection
International
Certifications
62-0410—04
Table 1. GENERAL SPECIFICATIONS
1: V/F (V/F control); 2: SVC (Sensorless Vector Control)
Reach up to 150% or above at 0.5Hz.
4 point adjustable V/F curve and square curve
5Hz
Heavy Duty: Max.170% torque current
±5%
230V series: 600.00Hz (55kw and above: 400.00Hz);
460V series: 600.00Hz (90KW and above: 400.00Hz)
Digital command:±0.01%, -10C~+40C, Analog command: ±0.1%, 25±10C
Digital command: 0.01Hz, Analog command: max. output frequency x 0.03/60 Hz (±11 bit)
Heavy duty: 120% of rated current for 1 minute;160% of rated current for 3 seconds
0~+10V, 4~20mA, 0~20mA, pulse input
Fault restart
Parameter copy
Speed search
Over-torque
detection
S-curve accel/
3-wire sequence
deccel
Slip compensation
Torque
compensation
Smart Stall
PID control (with
sleep function)
230V series
Model HCRDA0200B1000T (20HP) and above are PWM controlled
Model HCRDA0150B1000T (15HP) and below are on/off switch controlled
460V series
Model HCRDC0200B1000T and above are PWM controlled
Model HCRDC0150B1000T (15HP) and below are on/off switch controlled
Electronic thermal relay protection
Normal Duty: Over-current protection for 240% rated current
Current clamp Normal duty: 170~175%
230: drive will stop when DC-BUS voltage exceeds 410V
460: drive will stop when DC-BUS voltage exceeds 820V
Built-in temperature sensor
Stall prevention during acceleration, decceleration and running independently
Parameter setting up to 20 seconds
Leakage current is higher than 50% of rated current of the AC motor drive
CE, GB 12668.3
Dwell
BACnet COMM
Torque limit
16 preset speed
options
Auto-Tuning
Frequency upper/
(rotational,
lower limit settings
stationary)
JOG frequency
MODBus
communication
(RS-485 RJ45,
max. 115.2 kbps)
Energy saving
control
4
Momentary power
loss ride thru
Accel/Deccel. time
switch
Cooling fan on/off
switch
DC injection braking
at start/stop