HONEYWELL CORE DRIVE
DIGITAL SIGNAL COMMON TERMINAL WHILE
USING INTERNAL POWER TO RUN SINK MODE
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
3-PHASE POWER IS PROVIDED
FUSE/NO FUSE BREAKER
NFB
R(L1)
S(L2)
T(L3)
FACTORY SETTING:
PNP SOURCE
FWD/STOP
REV/STOP
PRESET SPD 1
PRESET SPD 2
PRESET SPD3
FACTORY
SETTING
PRESET SPD 4
EXT FAULT
FAULT RESET
NA
NA
POWER REMOVAL SAFETY FUNCTION
FOR EMERGENCY STOP
DIGITAL SIGNAL COMMON TERMINAL
+10V/20mA
0~10V/0~20mA
3
5KΩ
2
1
0-20mA/0~10V
0~+10V
ANALOG SIGNAL
COMMON TERMINAL
MAIN CIRCUIT (POWER)
TERMINALS
MODBUS RS-485
CONTROL
PIN 1~2, 7, 8:
TERMINALS
RESERVED
SHIELDED
PIN 3, 6: GND
LEADS &
PIN 4: SG-
CABLES
PIN 5: SG+
Fig. 8. Wiring Diagram for Frames A-C
Fig. 9. Source Mode with internal power (+24VDC)
DC CHOKE
BREAKING RESISTOR
(OPTIONAL)
(OPTIONAL)
JUMPER
R(L1)
U(T1)
S(L2)
V(T2)
T(L3)
W(T3)
DCM
COM
+24V
+24V
FWD
REV
RB1
MI1
MI2
RC1
MI3
RA2
MI4
MI5
MI6
RC2
MI7
MI8
RA3
DCM
RC3
S1
SCM
+10V
AVI1
AFM1
ACI
ACM
AVI2
AFM2
ACM
OPTION SLOT 1
8 1
8 1
OPTION SLOT 3
SG+
SG-
M1
M2
M8
DCM
COM
+24V
INTERNAL CIRCUIT
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
62-0410—04
M.S. Rev. 11-11
Printed in Taiwan
MOTOR
IM
3~
RA1 (RELAY OUT 1): RUN
RA2 (RELAY OUT 2): FAULT
RA3 (RELAY OUT 3): READY
MULTI-FUNCTION
OUTPUT TERMINALS
RA1
250VAC/6A
30VDC/6A
MULTI-FUNCTION OUTPUT
FREQUENCY TERMINALS
250VAC/5A
30VDC/5A
MULTI-FUNCTION OUTPUT
FREQUENCY TERMINALS
250VAC/5A
30VDC/5A
ANALOG MULTI-FUNCTION
OUTPUT TERMINAL
0~10V/0~20mA
ANALOG SIGNAL
COMMON TERMINAL
ANALOG MULTI-FUNCTION
OUTPUT TERMINAL
0~10V/0~20mA
COMMUNICATION EXTENSION CARD
I/O & RELAY EXTENSION CARD
MI: MULTIFUNCTION INPUT
AVI: ANALOGUE VOLTAGE INPUT
ACI: ANALOGUE CURRENT INPUT
M31490