Start-Up Wizard Guide - Honeywell CORE Drive Quick Start Manual

Hvac control variable frequency drive
Table of Contents

Advertisement

START-UP WIZARD GUIDE

Screen
Screen
#
Verbiage
1
Boot
Honeywell displayed for 3 seconds
Screen
2
Selection
Choose how to interact with the VFD:
Screen
Recommendation: Press function key F4 to
start the wizard
3
Select
Choose the keypad programming language
Language
Use UP and DOWN arrows to change from
default. Press ENTER to accept change.
F1 BACK up one menu (SAME function
throughout WIZARD)
F4 Next Parameter (SAME function
throughout WIZARD)
4
Clock Time
Select the time (Military) HH:MM:SS and date
and DATE
YY/MM/DD
5
Motor
Motor's rated voltage based upon Motor
Voltage
Name Plate data
6
Motor
Motor's rated current in FLA, Full Load AMPs
Current
based upon Motor Name Plate data. Do not
use motor service factor amperage for this
value.
7
Motor
Motor's rated frequency based upon Motor
FREQ
Name Plate data
8
Motor RPM Motor's rated RPM based upon Motor Name
Plate data
9
ACCEL
The time required to accelerate from the
TIME
motor's current speed reference to a new
speed reference
10
DECEL
The time required to decelerate from the
TIME
motor's current speed reference to a new
speed reference
11, 12,
PRESET
Present Speed options. On digital input
13
SPEED
closure the VFD will ignore the speed
1,2,3
reference from the analog input and will run at
the programmed speed.
14
Analog
Select the speed reference signal type.
Input
15
MIN
The minimum frequency at which the motor
Frequency
will operate
16
MAX
The maximum frequency at which the motor
Frequency
will operate
17
PRESS F4
Saves all parameter updates - VFD is ready
to SAVE
to operate
ALL
Table 11. Honeywell Commissioning Start-Up Wizard
Screen Description
N/A
F4: Initials the START UP WIZARD
Menu: redirects to MAIN MENU
ESC: redirects to MONITOR Screen
1. English
2. Spanish
3. Chinese
4. Portuguese
5. French
Use arrow keys to adjust. Press ENTER to save
changes, F4 to advance without changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Acceleration time is factory set for typical Fan and
Pump needs. Use arrow keys to adjust. Press ENTER
to save changes, F4 to advance without changes.
Decceleration time is factory set for typical Fan and
Pump needs. Use arrow keys to adjust. Press ENTER
to save changes, F4 to advance without changes.
With the use of MFI (Multifunction inputs) 1, 2, or 3 the
drive can be sent to the programmed speed on digital
input closure (Usage not required in the field). Adjust as
needed or press F4 to accept factory defaults.
0. 0-10V - Use AVI (Analog Voltage Input terminal)
1. 4-20mA - Use ACI (Analog current input terminals)
2. 2-10V - Use AVI
3. 0-20mA - Use ACI
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
F1 will escape the user back to the Selection Screen
again
F4 will save parameters and take the user to the display
screen
17
HONEYWELL CORE DRIVE
Screen options
62-0410—04