NOTE: Additional details and screen shots of the error messages can be found in the full manual.
ovn
ov at normal
DC BUS over-voltage at constant speed
SPD
(230V: DC 450V; 460V: DC 900V)
ovS
ov at stop
Hardware failure in voltage detection
LvA
Lv at accel
DC BUS voltage is less than
Pr.06-00 during acceleration
Lvd
Lv at decel
DC BUS voltage is less than
Pr.06-00 during decceleration
Lvn
Lv at normal
DC BUS voltage is less than
SPD
Pr.06-00 in constant speed
LvS
Lv at stop
DC BUS voltage is less than Pr.06-00 at stop 1. Check if the input voltage is normal
OrP
Phase
Phase Loss
lacked
oH1
IGBT over
IGBT overheating
heat
IGBT temperature exceeds protection level
1 to15HP: 90
20 to 100HP: 100
oH2
CAP over
Heatsink overheating
heat
Capacitance temperature exceeds 90
cause heatsink overheating.
oH3
Motor over
Motor overheating
heat
The AC motor drive detects that the internal
temperature exceeds
Pr.06-30 (PTC level)
PWR
Power RST
OFF
Power off
oL
Over load
Overload, The AC motor drive detects
excessive drive output current.
ot1
Over Torque
These two fault codes will be displayed when
1
output current exceeds the over-torque
detection level (Pr06-06 or Pr06-09) and
exceeds over-torque detection (Pr06-07 or
ot2
Over Torque
Pr06-10) and it is set to 2 or 4 in Pr06-05 or
2
Pr06-08.
uC
Under
Low current detection
Ampere
LMIT
Limit Error
Limit error
Table 14. Fault Codes and Descriptions
o
C
o
C
o
C
1. Check if the input voltage falls within the rated AC motor
drive input voltage range.
2. Check for possible voltage transients.
3. If DC BUS over-voltage due to regenerative voltage, please
increase the Decceleration Time or add an optional brake
resistor.
1. Check if the input voltage falls within the rated AC motor
drive input voltage range.
2. Check for possible voltage transients.
1. Check if the input voltage is normal
2. Check for possible sudden load
1. Check if the input voltage is normal
2. Check for possible sudden load
1. Check if the input voltage is normal
2. Check for possible sudden load
2. Check for possible sudden load
Check Power Source Input if all 3 input phases are connected
without loose contacts.
For models 40hp and above, please check if the fuse for the AC
input circuit is blown.
1. Ensure that the ambient temperature falls within the specified
temperature range.
2. Make sure that the ventilation holes are not obstructed.
3. Remove any foreign objects from the heatsinks and check for
possible dirty heat sink fins.
4. Check the fan and clean it.
5. Provide enough spacing for adequate ventilation.
1. Ensure that the ambient temperature falls within the specified
temperature range.
2. Make sure heat sink is not obstructed. Check if the fan is
operating
3. Check if there is enough ventilation clearance for AC motor
drive.
1. Make sure that the motor is not obstructed.
2. Ensure that the ambient temperature falls within the specified
temperature range.
3. Take the next higher power AC motor drive model.
Check if the motor is overloaded, if yes, replace with next larger
drive
1. Check whether the motor is overloaded.
2. Check whether motor rated current setting (Pr.05-01) is
suitable
3. Take the next higher power AC motor drive model.
Check Pr.06-61, Pr.06-62, Pr.06-63.