Appendix 3 Instructions For Ul And Cul - Mitsubishi Electric A800 Plus Instruction Manual

Separated converter type, roll to roll function
Hide thumbs Also See for A800 Plus:
Table of Contents

Advertisement

Appendix 3
(Standard to comply with: UL 508C, CSA C22.2 No.274-13)
General Precaution
CAUTION - Risk of Electric Shock -
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10
minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.
ATTENTION - Risque de choc électrique -
La durée de décharge du condensateur de bus est de 10 minutes. Avant de commencer le câblage ou l'inspection, mettez
l'appareil hors tension et attendez plus de 10 minutes.
Installation
The FR-A802 inverters with the below types of converter unit have been approved as products for use in enclosure.
Design the enclosure so that the surrounding air temperature, humidity and ambience of the inverter will satisfy the
specifications. (Refer to
page
 Branch circuit protection
For installation in the United States, Class T, Class J, Class CC, or Class L fuses must be provided, in accordance with the
National Electrical Code and any applicable local codes.
For installation in Canada, Class T, Class J, Class CC, or Class L fuses must be provided, in accordance with the
Canadian Electrical Code and any applicable local codes.
FR-CC2-[ ]
Rated fuse voltage (V)
Fuse allowable rating (A)
Wiring to the power supply and the motor
Refer to the National Electrical Code (Article 310) regarding the allowable current of the cable. Select the cable size for 125%
of the rated current according to the National Electrical Code (Article 430).
For wiring the input (R/L1, S/L2, T/L3) terminals of the converter unit and output (U, V, W) terminals of the inverter, use the UL
listed copper, stranded wires (rated at 75°C) and round crimp terminals. Crimp the terminals with the crimping tool
recommended by the terminal maker.
Short circuit ratings
Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 500 V maximum.
120
APPENDIX
Instructions for UL and cUL
20.)
H315K
H355K
500 V or more
1100
1200
H400K
H450K
H500K
1350
1500
1800
H560K
H630K
1800
1800